DX-9100 controllers identify themselves to their N2 supervisor as a Sys91 device type. The FAC3613 does not support identifying itself to its N2 supervisor as a Sys91 device type. As a result, you must use the CCT N2 Mapping interface to set the FAC3613 controller’s device type to VND, and reconfigure the N2 supervisor so that it is mapped as a VND device. See N2 Supervisor configuration for more information.

In addition, you must use the CCT N2 Mapping interface to manually create the N2 point mapping table.