The following table shows the legacy N2 controllers that can be functionally replaced with an N2 capable equipment controller, along with a suggested CGM, CVM, and FEC family controller replacement.
|
Legacy N2 Controller model |
Suggested CGM, CVM Controller replacement |
Suggested FEC Controller replacement |
|---|---|---|
|
VMA14xx |
CVM03050-0 VAV Box Controller |
VMA1832 Note: the VMA1832 model remains the best functional
replacement for a VMA1400
|
|
DX-9100 |
- |
FAC3613 + IOM (to meet I/O), DX-FAC-Adapter |
|
UNT1xx Note: For device
comparison details, see Replacing UNT Unitary Controllers
|
CGM04060-0 or CGM09090-0 General Purpose Controller |
FEC16xx or FEC26xx |
|
UNT11xx Note: For device
comparison details, see Replacing UNT Unitary Controllers
|
CGM04060-0 or CGM09090-0 General Purpose Controller |
FEC16xx or FEC26xx |
|
VAV1xx plus EDA/ATP |
CVM03050-0 VAV Box Controller |
VMA1832 for VAV box applications FEC16xx for Expansion I/O applications |
|
AHU |
CGM09090-0 General Purpose Controller plus XPM (to meet I/O) |
FAC3613 plus IOM (to meet I/O) |