How do I enable or disable the audible alarm feature? - Metasys - LIT-12011953 - Server - Metasys UI - 7.0.50

Metasys UI Help

Brand
Metasys
Product name
Metasys UI
Document type
User Guide
Document number
LIT-12011953
Version
7.0.50
Revision date
2024-03-19
Product status
Active
Language
English
If you have permission to modify your own user profile, you can enable or disable the audible alarm feature through My Profile using the steps below.
  1. Open My Profile from the User menu.
  2. Select the Details tab.
  3. In the Alarm Setting section, select or clear the checkbox for Enable Audible Alarm.
  4. Click or tap Save.

The setting change takes effect the next time you log in. Refresh your browser to have the change take effect immediately.

If you do not have permission to modify your own profile, an administrator can change your Enable Audible Alarm setting through the SMP UI using the steps below.
  1. Log in to the SMP UI as an administrator user.
  2. Go to Tools and Administrator.
  3. In the Roles and Users pane, right-click on a user and select Properties.
  4. Select the User Profile tab.
  5. Select or clear the checkbox for the Enable Audible Alarm option.
  6. Click OK.