| Performance rating | COV rate | Token loop time |
|---|---|---|
| Low | > 500 messages per minute | > 3,000 ms |
| Medium | Between 400 and 500 messages per minute | Between 2,000 and 3,000 ms |
| High | < 400 messages per minute | < 2,000 ms |