WRG1830/ZFR183x Pro Series Wireless Field Bus System - Metasys - LIT-12011832 - General System Information - Metasys System - 12.0

Metasys System Configuration Guide

Product
Building Automation Systems > Building Automation Systems > Metasys System
Document number
LIT-12011832
Version
12.0
Revision date
2025-07-23
Product status
Active

The WRG1830/ZFR183x Pro Series Wireless Field Bus System was introduced at Metasys Release 11.0, but it does not require Metasys 11.0.

The WRG1830/ZFR183x Pro Series Wireless Field Bus System uses different wireless coordinators, routers, and repeaters than the ZFR1810 Series Wireless Field Bus System and the WNC1800/ZFR182x Wireless Field Bus System. You cannot intermix WRG/183x, WNC/182x, or ZFR181x Series wireless devices on the same wireless PAN. However, you can have WRG/183x, WNC/182x, or ZFR181x wireless devices on separate PANs using separate coordinators under the same network engine. The ZFR183x Series wireless system connects to the network engine through Ethernet using BACnet/IP.

For more information about The WRG1830/ZFR183x Pro Series Wireless Field Bus System, refer to WRG1830/ZFR183x Pro Series Wireless Field Bus System Technical Bulletin (LIT-12013553).