Clearing the Audit Repository - Metasys - LIT-1201793 - Software Application - Metasys Site Management Portal - 12.0.50

Metasys Site Management Portal Help

Product
Building Automation Systems > Building Automation Systems > Metasys Site Management Portal
Document number
LIT-1201793
Version
12.0.50
Revision date
2023-06-02

Procedure

  1. Launch the Audit Viewer by selecting the desired Engine or Metasys Server from the Device Selection dialog box.
  2. Click anywhere in the Audit Viewer.
  3. Click Clear. All audit messages stored in that Audit Repository are cleared.

    Notes:

    • If you want to permanently store audit messages, click the Forward Messages button before clicking Clear.
    • For a validated ADX on an MVE system, an electronic signature with annotation is required before clearing the audit repository.