HVAC PRO Release 8.06 and later restricts the number of characters allowed in each controller name. HVAC PRO does not download, upload, commission, or retrieve information about the controller if the item name or controller name exceeds the 157 maximum characters limit.
The controller’s full name consists of the following: domain name, site name, equipment name, trunk name, and the actual controller’s name. The controller name appears in the following format:
Site_name:device_name.domain_name/N2 Trunk #.controller_name
|
Component |
Maximum Number of Characters Allowed by the Engine or SCT |
Maximum Viewable Characters |
Maximum Characters Allowed by HVAC PRO |
|
|---|---|---|---|---|
|
Site Name |
fewer than or equal to 32 |
30 |
47 Total |
157 |
|
Device Name |
fewer than or equal to 15 |
|||
|
Domain Name |
fewer than or equal to 64 |
|||
|
N2 Trunk Name |
fewer than or equal to 32 |
- |
||
|
Controller Name |
fewer than or equal to 32 |
|||