Defines the rules used to filter alarms. This attribute appears on the Email, Pager, Printer, and SNMP tabs. See Event Message Routing, Filtering, and Destinations in the Alarm and Event Management section for more information on filtering.
|
Filters |
Operators Allowed |
Values |
|---|---|---|
|
Acknowledge Required |
== or != |
True or False |
|
Current Status |
== or != |
Object Status Set |
|
Start Day of Week |
<, <=, >, >=, ==, or != |
Day of the week. Any value from Monday to Sunday |
|
Start Time |
<, <=, >, >=, ==, or != |
Time |
|
End Day of Week |
<, <=, >, >=, ==, or != |
Day of the week. Any value from Monday to Sunday |
|
End Time |
<, <=, >, >=, ==, or != |
Time |
|
Item Type |
== or != |
Object Type Set |
|
Authorization Category |
== or != |
Authorization Category Set |
|
Previous Status |
== or != |
Object Status Set |
|
Priority |
<, <=, >, >=, ==, or != Note: If you specify a filter with a value of >10,
you receive only alarms with priorities between 11 and 255.
|
Number value |
If you define multiple filters for a destination, the DDA combines all the criteria with an AND condition (all filter criteria must be met).