You can use wildcards for Week and Day entries. The Week and Day selection identifies a month, a week of the month, and a day of the week. The possible selections include any as the week of the month (that is, the entire month), 1 (Days 1–7), 2 (Days 8–14), 3 (Days 15–21), 4 (Days 22–28), 5 (Days 29–31), and 6 or last (the last seven days). The following table shows some sample wildcard week and day exceptions.
|
Month |
Week of Month |
Day of Week |
Meaning |
|---|---|---|---|
|
any |
any |
any |
Every day of the year |
|
any |
1 Days 1–7 |
Monday |
Monday of the first week of every month |
|
Jan |
any |
Tuesday |
Every Tuesday in January |
|
Feb |
2 Days 8–14 |
any |
Every day of the week in the second week of February |
|
any |
any |
Wednesday |
Wednesday of every week of every month |
|
Mar |
any |
any |
Every day of every week in March |
|
any |
3 Days 15–21 |
any |
Every day of the third week of every month |
|
Apr |
4 Days 22–28 |
Thursday |
Thursday in the fourth week of April |
|
any |
5 Days 29–31 |
any |
29th, 30th, and 31st (as applicable) of every month |
|
Jun |
6 or Last Last seven days |
Saturday |
Saturday in the last seven days of June |