Event Types, Event States, and Event Parameters are interrelated attributes.
|
Event Type |
Event State |
Event Parameters |
|---|---|---|
|
Change of Bitstring |
Normal Offnormal |
Time Delay Bitmask List of Bitstring Values |
|
Change of Character String |
Normal Offnormal |
Time Delay List of Values |
|
Change of State |
Normal Offnormal |
Time Delay List of Values |
|
Change of Value (COV) |
Normal |
Time Delay Bitmask COV Increment Note: Only one of either the Bitmask or the COV Increment property is used.
|
|
Command Failure |
Normal Offnormal |
Time Delay Feedback Property Reference |
|
Double Out of Range |
Normal High Limit Low Limit |
Time Delay Low Limit High Limit Deadband |
|
Floating Limit |
Normal High Limit Low Limit |
Time Delay Setpoint Reference Low Diff Limit Hi Diff Limit Deadband |
|
Out of Range |
Normal High Limit Low Limit |
Time Delay Low Limit High Limit Deadband |
|
Signed Out of Range |
Normal High Limit Low Limit |
Time Delay Low Limit High Limit Deadband |
|
Unsigned Out of Range |
Normal High Limit Low Limit |
Time Delay Low Limit High Limit Deadband |
|
Unsigned Range |
Normal High Limit Low Limit |
Time Delay Low Limit High Limit |