Event Types, Event States, and Event Parameters are interrelated attributes.

Note: Any Event Type generates a Fault Event State if the object referenced in the Object Property Reference becomes unreliable and the Object Property Ref attribute is linked to Reliability.
Table 1. Event Relationships

Event Type

Event State

Event Parameters

Change of Bitstring

Normal

Offnormal

Time Delay

Bitmask

List of Bitstring Values

Change of Character String

Normal

Offnormal

Time Delay

List of Values

Change of State

Normal

Offnormal

Time Delay

List of Values

Change of Value (COV)

Normal

Time Delay

Bitmask

COV Increment

Note: Only one of either the Bitmask or the COV Increment property is used.

Command Failure

Normal

Offnormal

Time Delay

Feedback Property Reference

Double Out of Range

Normal

High Limit

Low Limit

Time Delay

Low Limit

High Limit

Deadband

Floating Limit

Normal

High Limit

Low Limit

Time Delay

Setpoint Reference

Low Diff Limit

Hi Diff Limit

Deadband

Out of Range

Normal

High Limit

Low Limit

Time Delay

Low Limit

High Limit

Deadband

Signed Out of Range

Normal

High Limit

Low Limit

Time Delay

Low Limit

High Limit

Deadband

Unsigned Out of Range

Normal

High Limit

Low Limit

Time Delay

Low Limit

High Limit

Deadband

Unsigned Range

Normal

High Limit

Low Limit

Time Delay

Low Limit

High Limit