Symptom:

Excel is installed on to computer, but the report crashes before creating.

Data read successfully: retrieved 642 rows
Unexpected error: Exception from HRESULT: 0x800AC472
Error while closing Excel: Exception from HRESULT: 0x800AC472
Report creation terminated.

Cause:

Welcome and system pop-ups not being accepted for first access to the MS Application from MRE user.

Solution:

Log on the PC or server where MRE is installed with MRE user.

Open Excel and create a new file.

Accept or close all the welcome pop-up forms that the Excel application presents. Once all pop-ups cleared exit Excel.