The following data points related to bus diagnostics are captured by PVT and
display in the PVT dashboard, not the PVT client:
| Data point | Category |
|---|---|
| Bus health index | MSTP Trunk diagnostic tab |
| Bus performance Index | |
| Execution time | |
| Framing Errors | |
| Overrun Errors | |
| Header CRC Errors | |
| Data CRC Errors | |
| Reply Too Slow Datalink Errors | |
| Reply Too Slow Application Errors | |
| Internal Errors | |
| Buffer Overflows | |
| Lost Token | |
| Retries | |
| Max Output Queue Used | |
| Local Abort Tx | BACnet protocol diagnostic tab |
| Seg Retries Tx | |
| Reg Retries Tx | |
| Tx Record Count | |
| Rcv Record Count | |
| Record Count | |
| Tx Messages Discarded | |
| Rcv Messages Discarded | |
| Allocate Record Count | |
| Pending Queue Count | |
| Peak Pending Queue Count | |
| Unknown Queue Count | |
| Peak Unknown Queue Count | |
| Rcv Message Rate | |
| Transmits Per Minute | |
| Transactions Timeouts | |
| Net Messages Tx | |
| Net Messages Rcv | |
| Net Unknown Routes | |
| Net Rejects Rcv | |
| Net Routes Busy | |
| Net Unknown Msg Rcv | |
| Net Routed Messages |