Psychrometric logic blocks have 2 inputs, and you can add multiple connections to the output of the block.

Table 1. Psychrometric Blocks

Symbols

Description

Upper Input

Lower Input

EN-DP (EnDp)

Enthalpy - Dew Point

DB

DP

EN-RH (EnRh)

Enthalpy - Relative Humidity

DB

RH

RH-DP (RhDp)

Relative Humidity - Dew Point

DB

DP

RH-WB (RhWb)

Relative Humidity - Wet Bulb

DB

WB

WB-DP (WbDp)

Wet Bulb - Dew Point

DB

DP

WB-RH (WbRh)

Wet Bulb - Relative Humidity

DB

RH

ABH

Absolute Humidity

DB

RH

DP

Dew Point

DB

RH

See Editing Blocks in Edit Mode for information on editing Psychrometric blocks.