Load Command Interactions - Metasys - LIT-12011942 - Software Application - Metasys Open Data Server - 10.1

Metasys Open Data Server Help

Product
Building Automation Systems > Databases and Data Servers > Metasys Open Data Server
Document number
LIT-12011942
Version
10.1
Revision date
2019-10-14

Table 1 illustrates command interactions that pertain to Load objects.

Table 1. Load Command Interactions

Load Command(s) Currently in Effect

Load Command Not Allowed

Explanation

Shed

Shed

Load cannot be shed because it is already shed.

Shed + Locked

Comfort Override

or

Release Load

Lock must be removed with Unlock command.

Comfort Override

Shed

Comfort Override must be released with Release Comfort Override command.

Released + Locked

Shed

Lock must be removed with Unlock command.

Released + Locked

and

Comfort Override

Shed

Comfort Override must be released with Release Comfort Override command.

Lock must be removed with Unlock command.