Multiple Extension - Metasys - LIT-12011942 - Software Application - Metasys Open Data Server - 10.1

Metasys Open Data Server Help

Product
Building Automation Systems > Databases and Data Servers > Metasys Open Data Server
Document number
LIT-12011942
Version
10.1
Revision date
2019-10-14

About this task

To command multiple extension objects together (Global Commanding):

Procedure

  1. Use the Global Search feature to find the extension objects (Alarm, Trend, or Totalization). You may also open a saved Object List containing extension objects. See Interlocking a Trend Extension for more information.
  2. Select the extensions you wish to command (must be of the same type).
  3. Select Commands from the Action menu. The Global Commands dialog box appears.
  4. Choose the command to send.
  5. Click Send.