Schedule - Metasys - LIT-12013102 - M4-CGM09090-0 - M4-CGE09090-0 - M4-CGM04060-0 - M4-CGE04060-0 - Field Device - M4-CGM General Purpose Application Controller - 11.0

Metasys General Purpose Application Controllers Protocol Implementation Conformance Statement

Product
Controls > Field Controls > M4-CGM General Purpose Application Controller
Document number
LIT-12013102
Version
11.0
Revision date
2022-02-07

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Schedule

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

     

PRESENT_VALUE

X

   

85

 

X 1

 

EFFECTIVE_PERIOD

X

   

32

 

X

 

SCHEDULE_DEFAULT

X

   

174

 

X

 

LIST_OF_OBJECT_PROPERTY_REFERENCES

X

   

54

 

X

 

PRIORITY_FOR_WRITING

X

   

88

 

X

 

STATUS_FLAGS

X

   

111

     

RELIABILITY

X

   

103

     

OUT_OF_SERVICE

X

   

81

 

X

 

DESCRIPTION

 

X

 

28

 

X

40 characters max

WEEKLY_SCHEDULE

 

X

 

123

 

X

 

EXCEPTION_SCHEDULE

 

X

 

38

 

X

 

ALARM_STATE

   

X

1006

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

Character String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

0–249

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

   

PERFORM_INDEX

   

X

965

Unsigned

   

TODAYS_SCHEDULE

   

X

4198

List

   
1 Writable when OUT_OF_SERVICE is true.