Notification Class - Metasys - LIT-12013102 - M4-CGE04060-0 - M4-CGE09090-0 - M4-CGM04060-0 - M4-CGM09090-0 - Field Device - M4-CGM General Purpose Application Controller - 11.0

Metasys General Purpose Application Controllers Protocol Implementation Conformance Statement

Brand
Metasys
Product name
M4-CGM General Purpose Application Controller
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013102
Version
11.0
Revision date
2022-02-07
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Notification Class

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

     

ACK_REQUIRED

X

   

1

 

X

 

PRIORITY

X

   

86

 

X

 

RECIPIENT_LIST

X

   

102

 

X

 

DESCRIPTION

 

X

 

28

 

X

40 characters max

ALARM_STATE

   

X

1006

Enumerated

   

ENABLED

   

X

673

Enumerated

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

Character String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

0–249

ROUTE_TO_METASYS

   

X

32580

Boolean

X

 

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

   

SEND_NOTIFICATION_TO_SUPERVISOR

   

X

1095

Boolean

X

 

SEND_DEVICE_PROCESS_ ID

   

X

3052

Unsigned