Communication Protocol |
BACnet/SC or BACnet/IP | |
| Supervisory Device | All network engine model types at R9.0 or later | |
|
Modular Jacks |
6-Pin SA Bus with four communicating sensors, 8-pin RJ-45 jack for Ethernet connection | |
|
Point Types |
Signals Accepted |
Number of Points |
|
Universal Input (UI) |
Analog Input, Voltage Mode, 0–10 VDC Analog Input, Current Mode, 4–20 mA Analog Input, Resistive Mode, 0–2k ohm, resistance temperature detector (RTD) (1k NI [Johnson Controls], 1k PT, A99B SI), negative temperature coefficient (NTC) (10k Type L, 2.252k Type 2) Binary Input, Dry Contact Maintained Mode |
10 |
|
Binary Input (BI) |
Dry Contact Maintained Mode Pulse Counter/Accumulator Mode (High Speed), 100 Hz |
6 |
|
Analog Output (AO) |
Analog Output, Voltage Mode, 0–10 VDC Analog Current Mode, 4–20 mA |
4 |
|
Binary Output (BO) |
24 VAC Triac |
4 |
|
Configurable Output (CO) |
Analog Output, Voltage Mode, 0–10 VDC Binary Output Mode, 24 VAC Triac |
4 |