The status on the Data Precision Enhancement dialog box populates with a variety of messages throughout the database conversion process. These include general messages, warnings, and error messages. The following figure and tables describe the messages that can display in the status of the dialog box.
|
Message |
Description |
|---|---|
Active
|
The conversion is still active. |
Done
|
The conversion has finished successfully. |
Data type float already exists in database analog
tables
|
The database is already converted. |
|
Message |
Description |
|---|---|
Not enough free disk space on drive X. Temporarily about X or more are
required!
|
The database drive does not contain enough free disk space for the conversion. |
Warning: No free disk space information found via sql
|
The tool needs permission to read the free disk space information. |
SQL express database too big for conversion. Maximum supported size
for mdf: < 5 GB
|
The database size is too big for the conversion. |
|
Message |
Description |
|---|---|
Error, see details in Log
|
An error occurred and can be reviewed by clicking Show Log. |
Error during open database JCIHistorianDB
|
An open database error occurred after the tool started. Click Show Log to show error details. |