Table 1 describes the attributes used by the Damper Minimum Position Reset by CO2 modules.
|
Name |
Type 1 |
Description |
Default Value |
|---|---|---|---|
|
CO2 |
Represents the CO2 input. |
800 ppm |
|
|
MAD-MINPOS (Present Value) |
G, V |
Specifies the damper minimum position as determined by this module based on the CO2 value. |
Display Units: % |
|
Min Pos High Setpoint |
Defines the maximum damper position when the CO2 input equals the CO2 Reset B value. |
100.0% |
|
|
Min Pos Low Setpoint |
Defines the minimum damper position when the input equals the CO2 Reset A value. |
0.0% |
|
|
MOA-CO2RSTA (CO2 Reset A) |
Specifies that when CO2 is less than or equal to this value, the Damper Minimum equals the Min Pos Low Setpoint. |
800 ppm |
|
|
MOA-CO2RSTB (CO2 Reset B) |
Specifies that when CO2 is greater than or equal to this value, the Damper Minimum equals the Min Pos High Setpoint. |
1000 ppm |