Zone Damper w Staged Heating v50 - Metasys - Johnson Controls - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18
Important: As of Release 5.0, the Zone Damper w Staged Heating v50 module replaces the Zone Damper w Staged Heating module.

This module sequences the control of the zone dampers on a multizone unit with staged electric heating. The damper for the hot deck and cold deck are mechanically linked, so if the damper is open to one deck, the dampers closed to the other deck. These linked dampers modulate in sequence with the zone reheat to maintain a Zone Temperature setpoint. This module also incorporates tracking the overridden value of the actual output object (AO, PAO). The module resets the PIDs to default tuning parameters if the Reset PID Tuning input is not Normal. You can view and modify the modules in this group’s logic.