Off: The fan is off when the module is in this mode of operation.
-
Max: The relief fan turns at its maximum speed. The Relief Fan Percent Cmd output is set to 100%.
-
Min: The analog fan output (Relief Fan Percent Cmd) is zero, and the fan control output (Relief Fan OnOff) is on when the module is in this mode of operation.
-
Hold: Hold the outputs at their current position.
-
BS-P Control: The relief fan controls the building static pressure when the module receives this command. The module operates in the BS-P Control mode if the building static pressure is reliable.
|
Mode |
BSP Is Reliable |
State |
|---|---|---|
|
Off |
* |
Off |
|
Off |
* |
Off |
|
Min |
* |
Min |
|
Max |
* |
Max |
|
BS-P Control |
TRUE |
BS-P Control |
|
FALSE |
Off |