Open: Sets the output for maximum outdoor air. The Percent Cmd is set to 100%.
-
Close: Sets the output for zero outdoor air. The Percent Cmd is set to 0%.
-
Min: Sets the output for minimum outdoor air. The Percent Cmd is set to Minimum OA Pos.
-
Hold: Keeps the outputs at their current position. If the Output Overridden is true, then the Output Position input is passed to the Cooling Percent Cmd.
-
Control Econ: Adjusts the output to control the Process Variable. The Percent Cmd is adjusted between Minimum OA Pos and 100%.
-
Control Econ Limit: Adjusts the output to control the Low Limit Process Variable. The Percent Cmd is adjusted between Minimum OA Pos and 100%.
|
FSCS OAD Cmd |
Proof Of Airflow |
Process Variable Is Reliable |
Mode |
PID Tuning Reset |
State |
|---|---|---|---|---|---|
|
Open |
* |
* |
* |
* |
Open |
|
Close |
* |
* |
* |
* |
Close |
|
Auto |
* |
* |
Hold |
Reset 1st PID |
Control Econ Limit |
|
Fault |
* |
* |
* |
Close |
|
|
FALSE |
* |
* |
* |
Close |
|
|
TRUE |
TRUE |
Close |
* |
Close |
|
|
Open |
* |
Open |
|||
|
Min |
* |
Min |
|||
|
Hold |
* |
Hold |
|||
|
Control Econ |
* |
Control Econ |
|||
|
Control Econ Limit |
* |
Control Econ Limit |
|||
|
FALSE |
* |
* |
Close |
|
Mode |
State |
|---|---|
|
Close |
Close |
|
Open |
Open |
|
Min |
Min |
|
Hold |
Hold |
|
Control Econ |
Control |
|
Control Econ Limit |
Control |
|
Mode |
State |
|---|---|
|
Control Econ Limit |
Close |
|
Hold |
Hold |
|
Close |
No Limit Control |
|
Open |
No Limit Control |
|
Min |
No Limit Control |
|
Control Econ |
No Limit Control |