Bypass: Issue a fixed value to the Damper Percent Cmd (Shutdown, Box Flow Test, or Failsoft values).
-
Hold: Hold the Percent Cmd output at its current value.
-
Control Flow Unreliable: Adjust the Percent Cmd output using a pressure dependent mode of operation while either flow input is unreliable.
-
Control Flow Reliable: Adjust the Percent Cmd output to maintain the flow difference at the value of the Flow Differential SP.
|
Mode |
Flow Reliable |
Non-Zero SP |
State |
|---|---|---|---|
|
Open |
* |
* |
Bypass |
|
Close |
* |
* |
Bypass |
|
Hold |
* |
* |
Hold |
|
Control |
* |
False |
Bypass |
|
False |
True |
Control Flow Unreliable |
|
|
True |
True |
Control Flow Reliable |
|
|
Box Flow Test |
* |
* |
Bypass |
|
Failsoft |
* |
* |
Bypass |