Off: Sets the Common Percent Cmd to 0%.
-
Max: Sets the output for maximum and sets the Percent Cmd to 100%.
-
Control: Adjusts the output to control the process variable. If the process variable is reliable, the module controls the output to maintain the process variable at the setpoint.
-
Hold: Holds the outputs at their current position. If the Output Overridden is true, then the Output Position input is passed to the Cooling Percent Cmd.
|
Mode |
Delay |
Last State |
PID Tuning Reset |
State |
|---|---|---|---|---|
|
* |
True |
Max |
* |
Max |
|
* |
True |
Control |
* |
Control |
|
* |
True |
Hold |
* |
Hold |
|
Off |
* |
* |
* |
Off |
|
Max |
* |
* |
* |
Max |
|
Control |
* |
* |
* |
Control |
|
Hold |
* |
* |
Reset 1st PID |
Control |
|
Hold |
* |
* |
* |
Hold |