Primary States (Open Loop Tower Control with Low Limit) - Metasys - Johnson Controls - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18
  • No Limit Control: Disables the Low limit control.

  • Control Limit: Controls the low limit process variable to the low limit temperature setpoint.

Figure 1. Low Limit Control FSM