Optimized Damper Control (G36) (MASD) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18

The minimum outdoor air damper opens when the supply fan is proven on, the AHU is in Occupied Mode and the Minimum Outdoor Airflow Setpoint (MOAFLOW-SP) network AI is greater than zero. It is closed otherwise.