Freeze Protection (G36) (MASD) - Metasys - Johnson Controls - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18

There are three stages of freeze protection. The first stage modulates the heating valve to maintain a safe discharge air temperature. The second stage eliminates outdoor air ventilation in case heating is not available for any reason. The third stage shuts down the unit and activates coil valves and pumps to circulate water in case the second stage does not work, for example, stuck economizer damper.