Variable Speed Optimized Control (G36) (MASD) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18

The supply fan modulates to maintain the discharge air pressure setpoint (DAP-SP). A maximum speed is exposed to be used when the system is set up for a Return Fan with Volume Matching to prevent the supply air fan from overrunning the return air fan. Select the additional checkbox to indicate if the system has any reheat VAV boxes on the perimeter.