The following table describes the attributes used by the Unoccupied Sequencing (MZ) v100 modules:
|
Name |
Type 1 |
Description |
Default Value |
|---|---|---|---|
|
Application Mode |
Current Application Mode. |
Auto Set Name: AHU Effective App Mode |
|
|
Differential |
Amount Zone Temperature must exceed Unoccupied Setpoint to stop unoccupied control. |
2 °F | |
|
Occupancy |
Current Occupancy Mode. |
Occupied Set Name: Occ Effective |
|
|
Off During Unoccupied |
Selects the unoccupancy scheme. |
False |
|
|
State |
V |
Current state of the Hybrid Activity. |
Set Name: MZ Unocc Status State |
|
Unocc Cooling Setpoint |
Desired unoccupied cooling temperature setpoint. |
28 °C, 82 °F |
|
|
Unocc Heating Setpoint |
Desired unoccupied heating temperature setpoint. |
16 °C, 61 °F |
|
|
UNOCC-SATTIME (Satisfied Timer Duration) |
Time that the Zone Temperature must be within the limits before switching to Satisfied. |
30 Seconds |
|
|
UNOCC-STATE (Unocc Status) |
G, V |
Current Unoccupied Status. |
Set Name: MZ Unocc Status |
|
WarmupCooldown |
Current OST status. |
Normal Set Name: OST Warmup Cooldown |
|
|
Zone X Temperature |
Current temperature of Zone X (where X is1-8). |
22 °C, 72 °F |