|
Input |
Behavior When Input Is Not Reliable |
|---|---|
|
Duct Static Pressure 1 |
If both Duct Static Pressure 1 and Duct Static Pressure 2 inputs are unreliable, a shutdown Sequence is initiated. |
|
Duct Static Pressure 2 |
If both Duct Static Pressure 1 and Duct Static Pressure 2 inputs are unreliable, a shutdown Sequence is initiated. |