Reliability (2 Pipe Proportional Valve with Low Limit) - Metasys - Johnson Controls - LIT-12011147 - Software Application - Controller Configuration Tool - 13.1

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document number
LIT-12011147
Version
13.1
Revision date
2019-12-04
  • All inputs use their last reliable value while unreliable.

  • If the outdoor air temperature is unreliable while in the Low OA Temperature mode, the module switches to the Limited Max mode as shown in the Command Hierarchy table.

  • If the Low Limit Process Variable is unreliable while in the Remain In Control mode, the module switches to the Failsoft mode as shown in the Command Hierarchy table.