Off: Manual request to turn the fan off (typically made by network or zone sensor input). All three Fan OnOffs are set to Off.
-
Low: Manual request to turn the fan on at the low speed (typically made by network or zone sensor input). Fan OnOff 1 is set to On. The others are set to Off.
-
Medium: Manual request to turn the fan on at the medium speed (typically made by network or zone sensor input). Fan OnOff 2 is set to On. Fan OnOff 1 and 3 is set to Off.
-
High: Manual request to turn the fan on at the high speed (typically made by network or zone sensor input). Fan OnOff 3 is set to On and Fan OnOff 1 and 2 set to Off.
-
Auto-Off: Turn the fan off. All three Fan OnOffs are set to Off.
-
Auto-Low: Turn the fan on at no lower than Low speed. Compare the percent cmd inputs to the thresholds to determine the actual speed.
-
Auto-Medium: Turn the fan on at no lower than Medium speed. Compare the percent cmd inputs to the thresholds to determine the actual speed.
-
Auto-High: Turn the fan on at the high speed. Fan OnOff 3 is set to On and Fan OnOff 1 and 2 set to Off.
|
Mode |
Speed 2 |
Speed 3 |
State |
|---|---|---|---|
|
Off |
* |
* |
Off |
|
Low |
* |
* |
Low |
|
Medium |
* |
* |
Medium |
|
High |
* |
* |
High |
|
Auto-Off |
* |
* |
Off |
|
Auto-Low |
False |
False |
Low |
|
True |
False |
Medium |
|
|
* |
True |
High |
|
|
Auto-Medium |
* |
False |
Medium |
|
True |
High |
||
|
Auto-High |
* |
* |
High |