Reliability (Fan Supply Duct Static Control) - Metasys - Johnson Controls - LIT-12011147 - Software Application - Controller Configuration Tool - 13.1

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document number
LIT-12011147
Version
13.1
Revision date
2019-12-04

If the duct static pressure input is unreliable, the supply fan state changes to off as shown in the Command Hierarchy table.

All other inputs use the last reliable value while unreliable.