Off: The fan is off when the module is in this mode of operation.
-
Max: The return fan is commanded to its maximum speed. The Return Fan Percent Cmd output is set to 100%.
-
Min: The analog fan output (Return Fan Percent Cmd) is zero, and the fan control output (Return Fan OnOff) is on when the module is in this mode of operation.
-
Hold: Hold the outputs at their current position.
-
Failsoft: When in this mode of operation, the return fan tracks the supply fan. This mode is a fault mode entered if either flow sensor is unreliable.
-
VOL Control: When in this mode of operation, the return fan controls the return flow to maintain a differential flow (Volume Diff Setpoint) between the return and supply ducts. This operation is volume matching.
The following table illustrates the State Output dependencies on Mode and Flow Reliability inputs.
|
Mode |
Flow Reliable |
State |
|---|---|---|
|
Off |
* |
Off |
|
Min |
* |
Min |
|
Max |
* |
Max |
|
Hold |
* |
Hold |
|
VOL Control |
TRUE |
VOL Control |
|
FALSE |
Failsoft |
|
|
Zero VOL Control |
TRUE |
Zero VOL Control |
|
FALSE |
Failsoft |