Pressurize: This mode opens the OAD and closes the RAD.
-
Depressurize: This mode closes the RAD and OAD.
-
Close: This mode opens the RAD and closes the OAD.
-
Purge: This mode opens the OAD and closes the RAD.
-
Min OA: This mode moves the OAD and RAD to the appropriate position for minimum outdoor airflow.
-
Hold: This mode holds the dampers in their last position.
-
Ramp Min OA: This mode ramps the OAD to the minimum position and ramps the RAD to 100%.
-
Ramp Open: This mode ramps the OAD to 100% and the RAD to 0%.
-
T Control: This is the free cooling mode. The OAD and the RAD is modulated to allow outdoor air for cooling purposes. The OAD modulates from minimum position to 100%. If more outdoor air is required, the RAD modulates from 100% to 0%.
|
Mode |
FSCS OAD Cmd 1 |
PID Tuning Reset |
FSCS RAD Cmd1 |
State |
|---|---|---|---|---|
|
* |
!Auto |
* |
* |
FSCS Control |
|
* |
Auto |
* |
!Auto |
|
|
FSCS Control |
Auto |
* |
Auto |
|
|
Pressurize |
Auto |
* |
Auto |
Pressurize |
|
Depressurize |
Auto |
* |
Auto |
Depressurize |
|
Close |
Auto |
* |
Auto |
Close |
|
Purge |
Auto |
* |
Auto |
Purge |
|
Min OA |
Auto |
* |
Auto |
Min OA |
|
Hold |
Auto |
Reset 1st PID |
Auto |
T Control |
|
Hold |
Auto |
* |
Auto |
Hold |
|
Ramp Min OA |
Auto |
* |
Auto |
Ramp Min OA |
|
Ramp Open |
Auto |
* |
Auto |
Ramp Open |
|
T Control |
Auto |
* |
Auto |
T Control |