The following table describes the attributes used by this module.
| Name | Type 1 | Description | Default Value |
|---|---|---|---|
| Warmup Command | This input provides the network indication that Warmup is required. | False | |
| Vent Command |
This input provides the network indication that Vent Mode is required. |
False | |
| Purge Command |
This input provides the network indication that Purge Mode is required. |
False | |
| Shutdown Command |
This input provides the network indication that Shutdown is required |
False | |
| Water Flush Input | This input provides the network indication that a Water Flush is required. | False | |
| Zone Temperature | This input is the current Zone Temperature. | 0.0 | |
| Effective Cooling Setpoint | This input is the current cooling setpoint. | 0.0 | |
| Effective Heating Setpoint | This input is the current heating setpoint. | 0.0 | |
| Application Mode | V | This output is necessary to achieve the state desired based on the inputs.
|
Cool Only |
| Unit Enable | V | This output is used to close the box when Shutdown Closed is required. | Shutdown |
| WarmupCooldown | V |
This output indicates that a Warmup mode is requested. |
Normal |
1 C - Configuration Mode Only, G - Default Element (Generated State, if applicable), SC - Simulation and Commissioning Modes Only, V - Calculated Value (Outputs)