Finalizing ADS or ADX Turnkey settings - Metasys - LIT-12011177 - M4-ADXTK-TWR - M4-ADSTK-PC - M4-ADXTK-RCK - ADS/ADX Turnkey - 12.0
ADS/ADX Turnkey User Guide
- Product
- Building Automation Systems > Application Servers > ADS/ADX Turnkey
- Document number
- LIT-12011177
- Version
- 12.0
- Revision date
- 2022-05-20
Procedure
-
Log on to the
ADS/ADX
Site Management Portal.
-
Verify that no user views are currently open.
-
From the View menu, click Extended
Labels.
-
Double-click the Metasys site in the All Items
tree.
-
Click Edit in the display pane.
-
In the Name and Default ADS Repository
attributes, enter the new
ADS/ADX
name.
Note the case of each letter because the name is case-sensitive.
-
In the Time Zone attribute, set the time zone to the correct
zone.
-
Click Save.
-
From the Action menu, click Refresh All
Tabs. The site and
ADS/ADX
name
now match.
-
Exit the
ADS/ADX
Site Management Portal.
-
Restart the computer.
-
Go to
Finalizing Launcher settings.