Pressure values - Johnson Controls - LIT-12014272 - Valve - Venturi Valve

Venturi Air Valve with UVM1000 Installation Guide

Brand
Johnson Controls
Product name
Venturi Valve
Document type
Installation Guide
Document number
LIT-12014272
Revision date
2023-03-10
Language
English
The pressure value displays the converted value from the pressure input connection. The value is accurate if there is a calibrated pressure input and the calculated gain press sen and offset press sen values on the user settings tab are sent to the UVM board.
  1. To read the current pressure, click the Get Pressure button.
See the user settings tab for more information on how to calculate the gain and offset for the pressure sensor.