The float Pos value is the positional computed value of an attached floating actuator. The CW and CCW outputs open and close a floating actuator based on the Fit stroke time value under the User settings tab.

The UVM computes the effective position from the stroke time and how the actuator is open or closed. Floating actuators are not very accurate. This value may not match the actual actuator position.
  1. To read the current floating actuator assumed position, click the Get Time Float Pos button.