Table 1. Stainless Steel Trim Globe Valves with VA7800 Series Non-Spring-Return Electric Actuators
Valve code number Size,in. Cv Closeoff psig Non-spring return
Without auxiliary switches With two auxiliary switches
VA7810-AGA-2 on/off (floating) VA7810-HGA-2 (proportional) VA7810-AGC-2 on/off (floating) VA7810-HGC-2 (proportional)

Two-Way Push-Down-to-Close — NPT End Connections

VG7243CT

1/2

0.73

308

VG7243CT+71CAGA

VG7243CT+71CHGA

VG7243CT+71CAGC

VG7243CT+71CHGC

VG7243ET

1/2

1.8

308

VG7243ET+71CAGA

VG7243ET+71CHGA

VG7243ET+71CAGC

VG7243ET+71CHGC

VG7243GT

1/2

4.6

278

VG7243GT+71CAGA

VG7243GT+71CHGA

VG7243GT+71CAGC

VG7243GT+71CHGC

VG7243LT

3/4

7.3

177

VG7243LT+71CAGA

VG7243LT+71CHGA

VG7243LT+71CAGC

VG7243LT+71CHGC

VG7243NT

1

11.6

112

VG7243NT+71CAGA

VG7243NT+71CHGA

VG7243NT+71CAGC

VG7243NT+71CHGC

VG7243PT

1-1/4

18.5

68

VG7243PT+71CAGA

VG7243PT+71CHGA

VG7243PT+71CAGC

VG7243PT+71CHGC

VG7243RT

1-1/2

28.9

44

VG7243RT+71CAGA

VG7243RT+71CHGA

VG7243RT+71CAGC

VG7243RT+71CHGC

VG7243ST

2

46.2

28

VG7243ST+71CAGA

VG7243ST+71CHGA

VG7243ST+71CAGC

VG7243ST+71CHGC

VG7844CT

1/2

0.73

308 / 308

VG7844CT+71CAGA

VG7844CT+71CHGA

VG7844CT+71CAGC

VG7844CT+71CHGC

VG7844ET

1/2

1.8

308 / 308

VG7844ET+71CAGA

VG7844ET+71CHGA

VG7844ET+71CAGC

VG7844ET+71CHGC

VG7844GT

1/2

4.6

278 / 308

VG7844GT+71CAGA

VG7844GT+71CHGA

VG7844GT+71CAGC

VG7844GT+71CHGC

VG7844LT

3/4

7.3

177 / 197

VG7844LT+71CAGA

VG7844LT+71CHGA

VG7844LT+71CAGC

VG7844LT+71CHGC

VG7844NT

1

11.6

112 / 131

VG7844NT+71CAGA

VG7844NT+71CHGA

VG7844NT+71CAGC

VG7844NT+71CHGC

VG7844PT

1-1/4

18.5

68 / 75

VG7844PT+71CAGA

VG7844PT+71CHGA

VG7844PT+71CAGC

VG7844PT+71CHGC

VG7844RT

1-1/2

28.9

44 / 46

VG7844RT+71CAGA

VG7844RT+71CHGA

VG7844RT+71CAGC

VG7844RT+71CHGC

VG7844ST

2

46.2

28 / 29

VG7844ST+71CAGA

VG7844ST+71CHGA

VG7844ST+71CAGC

VG7844ST+71CHGC

Table 2. Stainless Steel Trim Globe Valves with VA7800 Series Spring-Return Electric Actuators
Valve code number Size,in. Cv Closeoff psig Spring return
Spring return stem up Spring return stem down
VA7820-HGA-21 Proportional without Switches VA7820-HGC-21 proportional with two switches VA7830-HGA-21 proportional without switches VA7830-HGC-21 proportional with two switches

Two-Way Push-Down-to-Close (Normally Open) — NPT End Connections

VG7243CT

1/2

0.73

308

VG7243CT+72CHGA

VG7243CT+72CHGC

   

VG7243ET

1/2

1.8

308

VG7243ET+72CHGA

VG7243ET+72CHGC

   

VG7243GT

1/2

4.6

278

VG7243GT+72CHGA

VG7243GT+72CHGC

   

VG7243LT

3/4

7.3

177

VG7243LT+72CHGA

VG7243LT+72CHGC

   

VG7243NT

1

11.6

112

VG7243NT+72CHGA

VG7243NT+72CHGC

   

VG7243PT

1-1/4

18.5

68

VG7243PT+72CHGA

VG7243PT+72CHGC

   

VG7243RT

1-1/2

28.9

44

VG7243RT+72CHGA

VG7243RT+72CHGC

   

VG7243ST

2

46.2

28

VG7243ST+72CHGA

VG7243ST+72CHGC

   

Two-Way Push-Down-to-Open (Normally Closed) — NPT End Connections

VG7443CT

1/2

0.73

308

VG7443CT+72CHGA

VG7443CT+72CHGC

   

VG7443ET

1/2

1.8

308

VG7443ET+72CHGA

VG7443ET+72CHGC

   

VG7443GT

1/2

4.6

308

VG7443GT+72CHGA

VG7443GT+72CHGC

   

VG7443LT

3/4

7.3

197

VG7443LT+72CHGA

VG7443LT+72CHGC

   

VG7443NT

1

11.6

131

VG7443NT+72CHGA

VG7443NT+72CHGC

   

VG7443PT

1-1/4

18.5

75

VG7443PT+72CHGA

VG7443PT+72CHGC

   

VG7443RT

1-1/2

28.9

46

VG7443RT+72CHGA

VG7443RT+72CHGC

   

VG7443ST

2

46.2

29

VG7443ST+72CHGA

VG7443ST+72CHGC

   

Three-Way Mixing — NPT End Connections

VG7844CT

1/2

0.73

308 / 308

VG7844CT+72CHGA

VG7844CT+72CHGC

VG7844CT+74CHGA

VG7844CT+74CHGC

VG7844ET

1/2

1.8

308 / 308

VG7844ET+72CHGA

VG7844ET+72CHGC

VG7844ET+74CHGA

VG7844ET+74CHGC

VG7844GT

1/2

4.6

278 / 308

VG7844GT+72CHGA

VG7844GT+72CHGC

VG7844GT+74CHGA

VG7844GT+74CHGC

VG7844LT

3/4

7.3

177 / 197

VG7844LT+72CHGA

VG7844LT+72CHGC

VG7844LT+74CHGA

VG7844LT+74CHGC

VG7844NT

1

11.6

112 / 131

VG7844NT+72CHGA

VG7844NT+72CHGC

VG7844NT+74CHGA

VG7844NT+74CHGC

VG7844PT

1-1/4

18.5

68 / 75

VG7844PT+72CHGA

VG7844PT+72CHGC

VG7844PT+74CHGA

VG7844PT+74CHGC

VG7844RT

1-1/2

28.9

44 / 46

VG7844RT+72CHGA

VG7844RT+72CHGC

VG7844RT+74CHGA

VG7844RT+74CHGC

VG7844ST

2

46.2

28 / 29

VG7844ST+72CHGA

VG7844ST+72CHGC

VG7844ST+74CHGA

VG7844ST+74CHGC

1 VA7820 and VA7830 spring-return actuators are shipped from the factory set for 0-10 VDC proportional control. These actuators have field-selectable switches that allow the actuators to be used for on/off control, or three-wire floating control.