Selection charts - Johnson Controls - LIT-1900087 - Pneumatic Actuator - Threaded Globe Valve and Actuator - VG7000 Series Stainless Steel Trim Globe Valves with V-3000 Pneumatic Actuators

VG7000 Series Stainless Steel Trim Globe Valves with V-3000 Pneumatic Actuators Catalog Page

Brand
Johnson Controls
Product name
VG7000 Series Stainless Steel Trim Globe Valves with V-3000 Pneumatic Actuators
Document type
Catalog Page
Document number
LIT-1900087
Revision date
2020-10-13
Language
English
Table 1. VG7000 Stainless Steel Trim Globe Valve with V-3000-8012 Exposed Pneumatic Actuator
Actuator Code Number V-3000-8012
Mounting Kit 1/2 in. and 3/4 in. VG7000-1001 VG7000-1002 VG7000-1003
1 in. and 1-1/4 in. VG7000-1004 VG7000-1005 VG7000-1006
1-1/2 in. and 2 in. VG7000-1007 VG7000-1008 VG7000-1009
Spring Range 3 psig to 6 psig 4 psig to 8 psig 9 psig to 13 psig
Valve Code Number Size, in. Cv Closeoff psig Code Number Closeoff psig Code Number Closeoff psig Code Number

Two-Way Normally Open — NPT End Connections (To specify a factory-mounted pneumatic positioner, add P to the end of the code number.)

VG7243CT

1/2

0.73

299

VG7243CT+3008B

255

VG7243CT+3008D

143

VG7243CT+3008E

VG7243ET

1/2

1.8

299

VG7243ET+3008B

255

VG7243ET+3008D

143

VG7243ET+3008E

VG7243GT

1/2

4.6

169

VG7243GT+3008B

144

VG7243GT+3008D

81

VG7243GT+3008E

VG7243LT

3/4

7.3

108

VG7243LT+3008B

92

VG7243LT+3008D

52

VG7243LT+3008E

VG7243NT

1

11.6

67

VG7243NT+3008B

57

VG7243NT+3008D

32

VG7243NT+3008E

VG7243PT

1-1/4

18.5

41

VG7243PT+3008B

35

VG7243PT+3008D

19

VG7243PT+3008E

Two-Way Normally Closed — NPT End Connections (To specify a factory-mounted pneumatic positioner, add P to the end of the code number.)

VG7443CT

1/2

0.73

75

VG7443CT+3008B

106

VG7443CT+3008D

261

VG7443CT+3008E

VG7443ET

1/2

1.8

75

VG7443ET+3008B

106

VG7443ET+3008D

261

VG7443ET+3008E

VG7443GT

1/2

4.6

36

VG7443GT+3008B

51

VG7443GT+3008D

126

VG7443GT+3008E

VG7443LT

3/4

7.3

22

VG7443LT+3008B

31

VG7443LT+3008D

75

VG7443LT+3008E

VG7443NT

1

11.6

13

VG7443NT+3008B

19

VG7443NT+3008D

49

VG7443NT+3008E

VG7443PT

1-1/4

18.5

7

VG7443PT+3008B

11

VG7443PT+3008D

28

VG7443PT+3008E

Three-Way Mixing — NPT End Connections (To specify a factory-mounted pneumatic positioner, add P to the end of the code number.)

VG7844CT

1/2

0.73

299 / 75

VG7844CT+3008B

255 / 106

VG7844CT+3008D

143 / 261

VG7844CT+3008E

VG7844ET

1/2

1.8

299 / 75

VG7844ET+3008B

255 / 106

VG7844ET+3008D

143 / 261

VG7844ET+3008E

VG7844GT

1/2

4.6

169 / 36

VG7844GT+3008B

144 / 51

VG7844GT+3008D

81 / 126

VG7844GT+3008E

VG7844LT

3/4

7.3

108 / 22

VG7844LT+3008B

92 / 31

VG7844LT+3008D

52 / 75

VG7844LT+3008E

VG7844NT

1

11.6

67 / 13

VG7844NT+3008B

57 / 19

VG7844NT+3008D

32 / 49

VG7844NT+3008E

VG7844PT

1-1/4

18.5

41 / 7

VG7844PT+3008B

35 / 11

VG7844PT+3008D

19 / 28

VG7844PT+3008E

Table 2. VG7000 Stainless Steel Trim Globe Valve with V-3000-8003 Enclosed Pneumatic Actuators
Actuator Code Number V-3000-8003
Mounting Kit 1/2 in. and 3/4 in. VG7000-1001 VG7000-1002 VG7000-1003
1 in. and 1-1/4 in. VG7000-1004 VG7000-1005 VG7000-1006
1-1/2 in. and 2 in. VG7000-1007 VG7000-1008 VG7000-1009
Spring Range 3 psig to 6 psig 4 psig to 8 psig 9 psig to 13 psig
Valve Code Number Size, in. Cv Closeoff psig Code Number Closeoff psig Code Number Closeoff psig Code Number

Two-Way Normally Open — NPT End Connections

VG7243CT

1/2

0.73

299

VG7243CT+3003B

255

VG7243CT+3003D

143

VG7243CT+3003E

VG7243ET

1/2

1.8

299

VG7243ET+3003B

255

VG7243ET+3003D

143

VG7243ET+3003E

VG7243GT

1/2

4.6

169

VG7243GT+3003B

144

VG7243GT+3003D

81

VG7243GT+3003E

VG7243LT

3/4

7.3

108

VG7243LT+3003B

92

VG7243LT+3003D

52

VG7243LT+3003E

VG7243NT

1

11.6

67

VG7243NT+3003B

57

VG7243NT+3003D

32

VG7243NT+3003E

VG7243PT

1-1/4

18.5

41

VG7243PT+3003B

35

VG7243PT+3003D

19

VG7243PT+3003E

Two-Way Normally Closed — NPT End Connections

VG7443CT

1/2

0.73

75

VG7443CT+3003B

106

VG7443CT+3003D

261

VG7443CT+3003E

VG7443ET

1/2

1.8

75

VG7443ET+3003B

106

VG7443ET+3003D

261

VG7443ET+3003E

VG7443GT

1/2

4.6

36

VG7443GT+3003B

51

VG7443GT+3003D

126

VG7443GT+3003E

VG7443LT

3/4

7.3

22

VG7443LT+3003B

31

VG7443LT+3003D

75

VG7443LT+3003E

VG7443NT

1

11.6

13

VG7443NT+3003B

19

VG7443NT+3003D

49

VG7443NT+3003E

VG7443PT

1-1/4

18.5

7

VG7443PT+3003B

11

VG7443PT+3003D

28

VG7443PT+3003E

Three-Way Mixing — NPT End Connections

VG7844CT

1/2

0.73

299 / 75

VG7844CT+3003B

255 / 106

VG7844CT+3003D

143 / 261

VG7844CT+3003E

VG7844ET

1/2

1.8

299 / 75

VG7844ET+3003B

255 / 106

VG7844ET+3003D

143 / 261

VG7844ET+3003E

VG7844GT

1/2

4.6

169 / 36

VG7844GT+3003B

144 / 51

VG7844GT+3003D

81 / 126

VG7844GT+3003E

VG7844LT

3/4

7.3

108 / 22

VG7844LT+3003B

92 / 31

VG7844LT+3003D

52 / 75

VG7844LT+3003E

VG7844NT

1

11.6

67 / 13

VG7844NT+3003B

57 / 19

VG7844NT+3003D

32 / 49

VG7844NT+3003E

VG7844PT

1-1/4

18.5

41 / 7

VG7844PT+3003B

35 / 11

VG7844PT+3003D

19 / 28

VG7844PT+3003E