Selection charts - Johnson Controls - LIT-1900123 - Electric Actuator - VG7000 Series Bronze Control Valve

VG7000 Series Brass Trim Globe Valves with VA-4233 Series Spring-Return Electric Actuators Catalog Page

Product
Valves and Actuators > Control Valves > VG7000 Series Bronze Control Valve
Document type
Catalog Page
Document number
LIT-1900123
Revision date
21/07/2020
Table 1. VG7000 Series brass trim globe valve assemblies with VA-4233 Series spring-return electric actuators, less auxiliary switches
Actuator code number VA-4233-AGA-2 VA-4233-BGA-2 VA-4233-GGA-2
Actuator input Floating On/off 0 VDC to 10 VDC proportional
Temperature range 35°F to 250°F (2°C to 121°C), 15 psig saturated steam
Valve code number Size, in. Cv Closeoff psig Spring return stem up

Two-way push-down-to-close — NPT end connections

VG7241CT

1/2

0.73

345

VG7241CT+423AGA

VG7241CT+423BGA

VG7241CT+423GGA

VG7241ET

1/2

1.8

345

VG7241ET+423AGA

VG7241ET+423BGA

VG7241ET+423GGA

VG7241GT

1/2

4.6

208

VG7241GT+423AGA

VG7241GT+423BGA

VG7241GT+423GGA

VG7241LT

3/4

7.3

132

VG7241LT+423AGA

VG7241LT+423BGA

VG7241LT+423GGA

VG7241NT

1

11.6

63

VG7241NT+423AGA

VG7241NT+423BGA

VG7241NT+423GGA

VG7241PT

1-1/4

18.5

38

VG7241PT+423AGA

VG7241PT+423BGA

VG7241PT+423GGA

Two-way push-down-to-open — NPT End Connections

VG7441CT

1/2

0.73

345

VG7441CT+423AGA

VG7441CT+423BGA

VG7441CT+423GGA

VG7441ET

1/2

1.8

345

VG7441ET+423AGA

VG7441ET+423BGA

VG7441ET+423GGA

VG7441GT

1/2

4.6

173

VG7441GT+423AGA

VG7441GT+423BGA

VG7441GT+423GGA

VG7441LT

3/4

7.3

103

VG7441LT+423AGA

VG7441LT+423BGA

VG7441LT+423GGA

VG7441NT

1

11.6

66

VG7441NT+423AGA

VG7441NT+423BGA

VG7441NT+423GGA

VG7441PT

1-1/4

18.5

38

VG7441PT+423AGA

VG7441PT+423BGA

VG7441PT+423GGA

Three-way mixing — NPT End Connections

VG7842CT

1/2

0.73

345 / 345

VG7842CT+423AGA

VG7842CT+423BGA

VG7842CT+423GGA

VG7842ET

1/2

1.8

345 / 345

VG7842ET+423AGA

VG7842ET+423BGA

VG7842ET+423GGA

VG7842GT

1/2

4.6

208 / 173

VG7842GT+423AGA

VG7842GT+423BGA

VG7842GT+423GGA

VG7842LT

3/4

7.3

132 / 103

VG7842LT+423AGA

VG7842LT+423BGA

VG7842LT+423GGA

VG7842NT

1

11.6

63 / 66

VG7842NT+423AGA

VG7842NT+423BGA

VG7842NT+423GGA

VG7842PT

1-1/4

18.5

38 / 38

VG7842PT+423AGA

VG7842PT+423BGA

VG7842PT+423GGA

Two-way push-down-to-close — Union Sweat End Connections

VG7281CT

1/2

0.73

345

VG7281CT+423AGA

VG7281CT+423BGA

VG7281CT+423GGA

VG7281ET

1/2

1.8

345

VG7281ET+423AGA

VG7281ET+423BGA

VG7281ET+423GGA

VG7281GT

1/2

4.6

208

VG7281GT+423AGA

VG7281GT+423BGA

VG7281GT+423GGA

VG7281LT

3/4

7.3

132

VG7281LT+423AGA

VG7281LT+423BGA

VG7281LT+423GGA

VG7281NT

1

11.6

63

VG7281NT+423AGA

VG7281NT+423BGA

VG7281NT+423GGA

VG7281PT

1-1/4

18.5

38

VG7281PT+423AGA

VG7281PT+423BGA

VG7281PT+423GGA

Two-way push-down-to-open — Union Sweat End Connections

VG7481CT

1/2

0.73

345

VG7481CT+423AGA

VG7481CT+423BGA

VG7481CT+423GGA

VG7481ET

1/2

1.8

345

VG7481ET+423AGA

VG7481ET+423BGA

VG7481ET+423GGA

VG7481GT

1/2

4.6

173

VG7481GT+423AGA

VG7481GT+423BGA

VG7481GT+423GGA

VG7481LT

3/4

7.3

103

VG7481LT+423AGA

VG7481LT+423BGA

VG7481LT+423GGA

VG7481NT

1

11.6

66

VG7481NT+423AGA

VG7481NT+423BGA

VG7481NT+423GGA

VG7481PT

1-1/4

18.5

38

VG7481PT+423AGA

VG7481PT+423BGA

VG7481PT+423GGA

Three-way mixing — Union Sweat End Connections

VG7882CT

1/2

0.73

345 / 345

VG7882CT+423AGA

VG7882CT+423BGA

VG7882CT+423GGA

VG7882ET

1/2

1.8

345 / 345

VG7882ET+423AGA

VG7882ET+423BGA

VG7882ET+423GGA

VG7882GT

1/2

4.6

208 / 173

VG7882GT+423AGA

VG7882GT+423BGA

VG7882GT+423GGA

VG7882LT

3/4

7.3

132 / 103

VG7882LT+423AGA

VG7882LT+423BGA

VG7882LT+423GGA

VG7882NT

1

11.6

63 / 66

VG7882NT+423AGA

VG7882NT+423BGA

VG7882NT+423GGA

VG7882PT

1-1/4

18.5

38 / 38

VG7882PT+423AGA

VG7882PT+423BGA

VG7882PT+423GGA

Two-way push-down-to-close — 3/8 in. Union Sweat End Connections

VG7271CT

1/2

0.73

345

VG7271CT+423AGA

VG7271CT+423BGA

VG7271CT+423GGA

VG7271ET

1/2

1.8

345

VG7271ET+423AGA

VG7271ET+423BGA

VG7271ET+423GGA

VG7271GT

1/2

4.6

208

VG7271GT+423AGA

VG7271GT+423BGA

VG7271GT+423GGA

Two-way push-down-to-open — 3/8 in. Union Sweat End Connections

VG7471CT

1/2

0.73

345

VG7471CT+423AGA

VG7471CT+423BGA

VG7471CT+423GGA

VG7471ET

1/2

1.8

345

VG7471ET+423AGA

VG7471ET+423BGA

VG7471ET+423GGA

VG7471GT

1/2

4.6

173

VG7471GT+423AGA

VG7471GT+423BGA

VG7471GT+423GGA

Three-way mixing — 3/8 in. Union Sweat End Connections

VG7872CT

1/2

0.73

345 / 345

VG7872CT+423AGA

VG7872CT+423BGA

VG7872CT+423GGA

VG7872ET

1/2

1.8

345 / 345

VG7872ET+423AGA

VG7872ET+423BGA

VG7872ET+423GGA

VG7872GT

1/2

4.6

208 / 173

VG7872GT+423AGA

VG7872GT+423BGA

VG7872GT+423GGA

Two-way push-down-to-close — 3/4 in. Union Sweat End Connections

VG7291CT

1/2

0.73

345

VG7291CT+423AGA

VG7291CT+423BGA

VG7291CT+423GGA

VG7291ET

1/2

1.8

345

VG7291ET+423AGA

VG7291ET+423BGA

VG7291ET+423GGA

VG7291GT

1/2

4.6

208

VG7291GT+423AGA

VG7291GT+423BGA

VG7291GT+423GGA

Two-way push-down-to-open — 3/4 in. Union Sweat End Connections

VG7491CT

1/2

0.73

345

VG7491CT+423AGA

VG7491CT+423BGA

VG7491CT+423GGA

VG7491ET

1/2

1.8

345

VG7491ET+423AGA

VG7491ET+423BGA

VG7491ET+423GGA

VG7491GT

1/2

4.6

173

VG7491GT+423AGA

VG7491GT+423BGA

VG7491GT+423GGA

Three-way mixing — 3/4 in. Union Sweat End Connections

VG7892CT

1/2

0.73

345 / 345

VG7892CT+423AGA

VG7892CT+423BGA

VG7892CT+423GGA

VG7892ET

1/2

1.8

345 / 345

VG7892ET+423AGA

VG7892ET+423BGA

VG7892ET+423GGA

VG7892GT

1/2

4.6

208 / 173

VG7892GT+423AGA

VG7892GT+423BGA

VG7892GT+423GGA

Table 2. VG7000 Series brass trim valve assemblies with VA-4233 Series spring-return electric actuators and two auxiliary switches (Part 1 of 2)
Actuator code number VA-4233-AGC-2 VA-4233-BGC-2 VA-4233-GGC-2
Actuator input Floating On/off 0 VDC to 10 VDC proportional
Temperature range 35°F to 250°F (2°C to 121°C), 15 psig saturated steam
Valve code number Size, in. Cv Closeoff psig Spring return stem up

Two-way push-down-to-close — NPT End Connections

VG7241CT

1/2

0.73

345

VG7241CT+423AGC

VG7241CT+423BGC

VG7241CT+423GGC

VG7241ET

1/2

1.8

345

VG7241ET+423AGC

VG7241ET+423BGC

VG7241ET+423GGC

VG7241GT

1/2

4.6

208

VG7241GT+423AGC

VG7241GT+423BGC

VG7241GT+423GGC

VG7241LT

3/4

7.3

132

VG7241LT+423AGC

VG7241LT+423BGC

VG7241LT+423GGC

VG7241NT

1

11.6

63

VG7241NT+423AGC

VG7241NT+423BGC

VG7241NT+423GGC

VG7241PT

1-1/4

18.5

38

VG7241PT+423AGC

VG7241PT+423BGC

VG7241PT+423GGC

Two-way push-down-to-open — NPT End Connections

VG7441CT

1/2

0.73

345

VG7441CT+423AGC

VG7441CT+423BGC

VG7441CT+423GGC

VG7441ET

1/2

1.8

345

VG7441ET+423AGC

VG7441ET+423BGC

VG7441ET+423GGC

VG7441GT

1/2

4.6

173

VG7441GT+423AGC

VG7441GT+423BGC

VG7441GT+423GGC

VG7441LT

3/4

7.3

103

VG7441LT+423AGC

VG7441LT+423BGC

VG7441LT+423GGC

VG7441NT

1

11.6

66

VG7441NT+423AGC

VG7441NT+423BGC

VG7441NT+423GGC

VG7441PT

1-1/4

18.5

38

VG7441PT+423AGC

VG7441PT+423BGC

VG7441PT+423GGC

Three-way mixing — NPT End Connections

VG7842CT

1/2

0.73

345 / 345

VG7842CT+423AGC

VG7842CT+423BGC

VG7842CT+423GGC

VG7842ET

1/2

1.8

345 / 345

VG7842ET+423AGC

VG7842ET+423BGC

VG7842ET+423GGC

VG7842GT

1/2

4.6

208 / 173

VG7842GT+423AGC

VG7842GT+423BGC

VG7842GT+423GGC

VG7842LT

3/4

7.3

132 / 103

VG7842LT+423AGC

VG7842LT+423BGC

VG7842LT+423GGC

VG7842NT

1

11.6

63 / 66

VG7842NT+423AGC

VG7842NT+423BGC

VG7842NT+423GGC

VG7842PT

1-1/4

18.5

38 / 38

VG7842PT+423AGC

VG7842PT+423BGC

VG7842PT+423GGC

Two-way push-down-to-close — Union Sweat End Connections

VG7281CT

1/2

0.73

345

VG7281CT+423AGC

VG7281CT+423BGC

VG7281CT+423GGC

VG7281ET

1/2

1.8

345

VG7281ET+423AGC

VG7281ET+423BGC

VG7281ET+423GGC

VG7281GT

1/2

4.6

208

VG7281GT+423AGC

VG7281GT+423BGC

VG7281GT+423GGC

VG7281LT

3/4

7.3

132

VG7281LT+423AGC

VG7281LT+423BGC

VG7281LT+423GGC

VG7281NT

1

11.6

63

VG7281NT+423AGC

VG7281NT+423BGC

VG7281NT+423GGC

VG7281PT

1-1/4

18.5

38

VG7281PT+423AGC

VG7281PT+423BGC

VG7281PT+423GGC

Two-way push-down-to-open — Union Sweat End Connections

VG7481CT

1/2

0.73

345

VG7481CT+423AGC

VG7481CT+423BGC

VG7481CT+423GGC

VG7481ET

1/2

1.8

345

VG7481ET+423AGC

VG7481ET+423BGC

VG7481ET+423GGC

VG7481GT

1/2

4.6

173

VG7481GT+423AGC

VG7481GT+423BGC

VG7481GT+423GGC

VG7481LT

3/4

7.3

103

VG7481LT+423AGC

VG7481LT+423BGC

VG7481LT+423GGC

VG7481NT

1

11.6

66

VG7481NT+423AGC

VG7481NT+423BGC

VG7481NT+423GGC

VG7481PT

1-1/4

18.5

38

VG7481PT+423AGC

VG7481PT+423BGC

VG7481PT+423GGC

Three-way mixing — Union Sweat End Connections

VG7882CT

1/2

0.73

345 / 345

VG7882CT+423AGC

VG7882CT+423BGC

VG7882CT+423GGC

VG7882ET

1/2

1.8

345 / 345

VG7882ET+423AGC

VG7882ET+423BGC

VG7882ET+423GGC

VG7882GT

1/2

4.6

208 / 173

VG7882GT+423AGC

VG7882GT+423BGC

VG7882GT+423GGC

VG7882LT

3/4

7.3

132 / 103

VG7882LT+423AGC

VG7882LT+423BGC

VG7882LT+423GGC

VG7882NT

1

11.6

63 / 66

VG7882NT+423AGC

VG7882NT+423BGC

VG7882NT+423GGC

VG7882PT

1-1/4

18.5

38 / 38

VG7882PT+423AGC

VG7882PT+423BGC

VG7882PT+423GGC

Two-way push-down-to-close — 3/8 in. Union Sweat End Connections

VG7271CT

1/2

0.73

345

VG7271CT+423AGC

VG7271CT+423BGC

VG7271CT+423GGC

VG7271ET

1/2

1.8

345

VG7271ET+423AGC

VG7271ET+423BGC

VG7271ET+423GGC

VG7271GT

1/2

4.6

208

VG7271GT+423AGC

VG7271GT+423BGC

VG7271GT+423GGC

Two-way push-down-to-open — 3/8 in. Union Sweat End Connections

VG7471CT

1/2

0.73

345

VG7471CT+423AGC

VG7471CT+423BGC

VG7471CT+423GGC

VG7471ET

1/2

1.8

345

VG7471ET+423AGC

VG7471ET+423BGC

VG7471ET+423GGC

VG7471GT

1/2

4.6

173

VG7471GT+423AGC

VG7471GT+423BGC

VG7471GT+423GGC

Three-way mixing — 3/8 in. Union Sweat End Connections

VG7872CT

1/2

0.73

345 / 345

VG7872CT+423AGC

VG7872CT+423BGC

VG7872CT+423GGC

VG7872ET

1/2

1.8

345 / 345

VG7872ET+423AGC

VG7872ET+423BGC

VG7872ET+423GGC

VG7872GT

1/2

4.6

208 / 173

VG7872GT+423AGC

VG7872GT+423BGC

VG7872GT+423GGC

Two-way push-down-to-close — 3/4 in. Union Sweat End Connections

VG7291CT

1/2

0.73

345

VG7291CT+423AGC

VG7291CT+423BGC

VG7291CT+423GGC

VG7291ET

1/2

1.8

345

VG7291ET+423AGC

VG7291ET+423BGC

VG7291ET+423GGC

VG7291GT

1/2

4.6

208

VG7291GT+423AGC

VG7291GT+423BGC

VG7291GT+423GGC

Two-way push-down-to-open — 3/4 in. Union Sweat End Connections

VG7491CT

1/2

0.73

345

VG7491CT+423AGC

VG7491CT+423BGC

VG7491CT+423GGC

VG7491ET

1/2

1.8

345

VG7491ET+423AGC

VG7491ET+423BGC

VG7491ET+423GGC

VG7491GT

1/2

4.6

173

VG7491GT+423AGC

VG7491GT+423BGC

VG7491GT+423GGC

Three-way mixing — 3/4 in. Union Sweat End Connections

VG7892CT

1/2

0.73

345 / 345

VG7892CT+423AGC

VG7892CT+423BGC

VG7892CT+423GGC

VG7892ET

1/2

1.8

345 / 345

VG7892ET+423AGC

VG7892ET+423BGC

VG7892ET+423GGC

VG7892GT

1/2

4.6

208 / 173

VG7892GT+423AGC

VG7892GT+423BGC

VG7892GT+423GGC