Features - Johnson Controls - LIT-1900222 - Electric Actuator - Flanged Globe or Ball Valve and Actuator - VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Spring-Return Electric Actuators without Switches

VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Spring-Return Electric Actuators without Switches Catalog Page

Brand
Johnson Controls
Product name
VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Spring-Return Electric Actuators without Switches
Document type
Catalog Page
Document number
LIT-1900222
Revision date
2021-02-18
Language
English
  • Forged brass body — provides 580 psig static pressure rating.
  • 200 psi closeoff pressure rating — provides tight shutoff.
  • Graphite-reinforced Polytetrafluoroethylene (PTFE) seats — include 15 per cent graphite-reinforced ball seals, providing better wear resistance.
  • 300 series stainless steel ball and stem assembly — tolerates high-temperature water or 15 psi saturated steam with fluid temperatures of -22°F to 284 ° F (-30°C to 140 ° C) or where a higher degree of corrosion protection is desired.
  • 500:1 rangeability — provides accurate control under all load conditions.