Selection charts - Johnson Controls - LIT-1900220 - Electric Actuator - Flanged Globe or Ball Valve and Actuator - VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring Return Electric Actuators

VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring Return Electric Actuators Catalog Page

Brand
Johnson Controls
Product name
VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring Return Electric Actuators
Document type
Catalog Page
Document number
LIT-1900220
Revision date
2021-02-15
Language
English
Table 1. Two-way stainless steel trim ball valves, non-spring return, VA9104 Series electric actuators without switches
Fluid temperatures: -4°F to 212°F (-20°C to 100°C) not rated for steam service AC 24 V
On/off and/or floating without timeout 1 On/off and/or floating with timeout DC 0 to 10 V proportional
Valve Size, in. Cv Characterizing disk Closeoff psig

Actuators with M3 Screw Terminals

VA9104-AGA-3S

VA9104-IGA-3S

VA9104-GGA-3S

VG1245AA

1/2

0.3 Yes

200

VG1245AA+9T4AGA - VG1245AA+9T4GGA
VG1245AB 0.5 Yes VG1245AB+9T4AGA - VG1245AB+9T4GGA
VG1245AC 0.8 Yes VG1245AC+9T4AGA - VG1245AC+9T4GGA

VG1245AD

1.2

Yes

VG1245AD+9T4AGA

VG1245AD+9T4IGA

VG1245AD+9T4GGA

VG1245AE

1.9

Yes

VG1245AE+9T4AGA

VG1245AE+9T4IGA

VG1245AE+9T4GGA

VG1245AF

2.9

Yes

VG1245AF+9T4AGA

VG1245AF+9T4IGA

VG1245AF+9T4GGA

VG1245AG

4.7

Yes

VG1245AG+9T4AGA

VG1245AG+9T4IGA

VG1245AG+9T4GGA

VG1245AL

7.4

Yes

VG1245AL+9T4AGA

VG1245AL+9T4IGA

VG1245AL+9T4GGA

VG1245AN

11.7

No

VG1245AN+9T4AGA

VG1245AN+9T4IGA

VG1245AN+9T4GGA

VG1245BG

3/4

4.7

Yes

200

VG1245BG+9T4AGA

VG1245BG+9T4IGA

VG1245BG+9T4GGA

VG1245BL

7.4

Yes

VG1245BL+9T4AGA

VG1245BL+9T4IGA

VG1245BL+9T4GGA

VG1245BN

11.7

No

VG1245BN+9T4AGA

VG1245BN+9T4IGA

VG1245BN+9T4GGA

VG1245CL

1

7.4

Yes

200

VG1245CL+9T4AGA

VG1245CL+9T4IGA

VG1245CL+9T4GGA

VG1245CN

11.7

Yes

VG1245CN+9T4AGA

VG1245CN+9T4IGA

VG1245CN+9T4GGA

VG1245CP

18.7

No

VG1245CP+9T4AGA

VG1245CP+9T4IGA

VG1245CP+9T4GGA

Actuators with 120 in. (3.05 m) 18 AWG plenum cable

VA9104-AGA-2S

VA9104-IGA-2S

VA9104-GGA-2S

VG1245AA

1/2

0.3 Yes

200

VG1245AA+9A4AGA - VG1245AA+9A4GGA
VG1245AB 0.5 Yes VG1245AB+9A4AGA - VG1245AB+9A4GGA
VG1245AC 0.8 Yes VG1245AC+9A4AGA - VG1245AC+9A4GGA

VG1245AD

1.2

Yes

VG1245AD+9A4AGA

VG1245AD+9A4IGA

VG1245AD+9A4GGA

VG1245AE

1.9

Yes

VG1245AE+9A4AGA

VG1245AE+9A4IGA

VG1245AE+9A4GGA

VG1245AF

2.9

Yes

VG1245AF+9A4AGA

VG1245AF+9A4IGA

VG1245AF+9A4GGA

VG1245AG

4.7

Yes

VG1245AG+9A4AGA

VG1245AG+9A4IGA

VG1245AG+9A4GGA

VG1245AL

7.4

Yes

VG1245AL+9A4AGA

VG1245AL+9A4IGA

VG1245AL+9A4GGA

VG1245AN

11.7

No

VG1245AN+9A4AGA

VG1245AN+9A4IGA

VG1245AN+9A4GGA

VG1245BG

3/4

4.7

Yes

200

VG1245BG+9A4AGA

VG1245BG+9A4IGA

VG1245BG+9A4GGA

VG1245BL

7.4

Yes

VG1245BL+9A4AGA

VG1245BL+9A4IGA

VG1245BL+9A4GGA

VG1245BN

11.7

No

VG1245BN+9A4AGA

VG1245BN+9A4IGA

VG1245BN+9A4GGA

VG1245CL

1

7.4

Yes

200

VG1245CL+9A4AGA

VG1245CL+9A4IGA

VG1245CL+9A4GGA

VG1245CN

11.7

Yes

VG1245CN+9A4AGA

VG1245CN+9A4IGA

VG1245CN+9A4GGA

VG1245CP

18.7

No

VG1245CP+9A4AGA

VG1245CP+9A4IGA

VG1245CP+9A4GGA

Table 2. Two-way stainless steel trim ball valves, non-spring return, VA9104 Series electric actuators without switches with optional M9000-561 Thermal Barrier
Fluid temperatures: -22°F to 284°F (-30°C to 140°C) water and 15 psi saturated steam AC 24 V
On/off and/or floating without timeout 2 On/off and/or floating with timeout DC 0 to 10 V proportional
Valve Size, in. Cv Characterizing disk Closeoff psig

Actuators with M3 screw terminals with M9000-561 Thermal Barrier installed

VA9104-AGA-3S

VA9104-IGA-3S

VA9104-GGA-3S

VG1245AA

1/2

0.3 Yes

200

VG1245AAH9T4AGA - VG1245AAH9T4GGA
VG1245AB 0.5 Yes VG1245ABH9T4AGA - VG1245ABH9T4GGA
VG1245AC 0.8 Yes VG1245ACH9T4AGA - VG1245ACH9T4GGA

VG1245AD

1.2

Yes

VG1245ADH9T4AGA

VG1245ADH9T4IGA

VG1245ADH9T4GGA

VG1245AE

1.9

Yes

VG1245AEH9T4AGA

VG1245AEH9T4IGA

VG1245AEH9T4GGA

VG1245AF

2.9

Yes

VG1245AFH9T4AGA

VG1245AFH9T4IGA

VG1245AFH9T4GGA

VG1245AG

4.7

Yes

VG1245AGH9T4AGA

VG1245AGH9T4IGA

VG1245AGH9T4GGA

VG1245AL

7.4

Yes

VG1245ALH9T4AGA

VG1245ALH9T4IGA

VG1245ALH9T4GGA

VG1245AN

11.7

No

VG1245ANH9T4AGA

VG1245ANH9T4IGA

VG1245ANH9T4GGA

VG1245BG

3/4

4.7

Yes

200

VG1245BGH9T4AGA

VG1245BGH9T4IGA

VG1245BGH9T4GGA

VG1245BL

7.4

Yes

VG1245BLH9T4AGA

VG1245BLH9T4IGA

VG1245BLH9T4GGA

VG1245BN

11.7

No

VG1245BNH9T4AGA

VG1245BNH9T4IGA

VG1245BNH9T4GGA

VG1245CL

1

7.4

Yes

200

VG1245CLH9T4AGA

VG1245CLH9T4IGA

VG1245CLH9T4GGA

VG1245CN

11.7

Yes

VG1245CNH9T4AGA

VG1245CNH9T4IGA

VG1245CNH9T4GGA

VG1245CP

18.7

No

VG1245CPH9T4AGA

VG1245CPH9T4IGA

VG1245CPH9T4GGA

Actuators with 120 in. (3.05 m) 18 AWG plenum cable with M9000-561 Thermal Barrier installed

VA9104-AGA-2S

VA9104-IGA-2S

VA9104-GGA-2S

VG1245AA

1/2

0.3 Yes

200

VG1245AAH9A4AGA

-

VG1245AAH9A4AGA

VG1245AB 0.5 Yes

VG1245ABH9A4AGA

-

VG1245ABH9A4AGA

VG1245AC 0.8 Yes

VG1245ACH9A4AGA

-

VG1245ACH9A4AGA

VG1245AD

1.2

Yes

VG1245ADH9A4AGA

VG1245ADH9A4IGA

VG1245ADH9A4GGA

VG1245AE

1.9

Yes

VG1245AEH9A4AGA

VG1245AEH9A4IGA

VG1245AEH9A4GGA

VG1245AF

2.9

Yes

VG1245AFH9A4AGA

VG1245AFH9A4IGA

VG1245AFH9A4GGA

VG1245AG

4.7

Yes

VG1245AGH9A4AGA

VG1245AGH9A4IGA

VG1245AGH9A4GGA

VG1245AL

7.4

Yes

VG1245ALH9A4AGA

VG1245ALH9A4IGA

VG1245ALH9A4GGA

VG1245AN

11.7

No

VG1245ANH9A4AGA

VG1245ANH9A4IGA

VG1245ANH9A4GGA

VG1245BG

3/4

4.7

Yes

200

VG1245BGH9A4AGA

VG1245BGH9A4IGA

VG1245BGH9A4GGA

VG1245BL

7.4

Yes

VG1245BLH9A4AGA

VG1245BLH9A4IGA

VG1245BLH9A4GGA

VG1245BN

11.7

No

VG1245BNH9A4AGA

VG1245BNH9A4IGA

VG1245BNH9A4GGA

VG1245CL

1

7.4

Yes

200

VG1245CLH9A4AGA

VG1245CLH9A4IGA

VG1245CLH9A4GGA

VG1245CN

11.7

Yes

VG1245CNH9A4AGA

VG1245CNH9A4IGA

VG1245CNH9A4GGA

VG1245CP

18.7

No

VG1245CPH9A4AGA

VG1245CPH9A4IGA

VG1245CPH9A4GGA

Table 3. Two-way stainless steel trim ball valves, non-spring return, VA9300 Series electric actuators without switches
Fluid temperatures:-4°F to 212°F (-20°C to 100°C) not rated for steam service AC/DC 24 V
On/Off Floating DC 0(2) to 10 V

proportional

Valve

Size, in.

Cv

Characterizing disk

Closeoff psi

VA9310-HGA-2 with M9000-561 Thermal Barrier

VG1245DN

1-1/4

11.7

Yes

200

VG1245DN+910HGA

VG1245DP

18.7

Yes

VG1245DP+910HGA

VG1245DR

29.2

No

VG1245DR+910HGA

VG1245EP

1-1/2

18.7 Yes

200

VG1245EP+910HGA

VG1245ER

29.2 Yes

VG1245ER+910HGA

VG1245ES

46.8

No

VG1245ES+910HGA

VG1245FR

2

29.2 Yes

200

VG1245FR+910HGA

VG1245FS

48.8 Yes

VG1245FS+910HGA

VG1245FT

73.7

No

VG1245FT+910HGA

Table 4. Two-way stainless steel trim ball valves, non-spring return, VA9300 Series electric actuators with switches
Fluid temperatures:-4°F to 212°F (-20°C to 100°C) not rated for steam service AC/DC 24 V
On/Off Floating DC 0(2) to 10 V

proportional

Valve

Size, in.

Cv

Characterizing disk

Closeoff psi

VA9310-HGA-2 Actuator with M9300-2 Switch Kit 3

VG1245AA

1/2

0.3 Yes

200

VG1245AA+910HGC

VG1245AB 0.5 Yes VG1245AB+910HGC
VG1245AC 0.8 Yes VG1245AC+910HGC
VG1245AD 1.2 Yes VG1245AD+910HGC

VG1245AE

1.9

Yes

VG1245AE+910HGC

VG1245AF

2.9

Yes

VG1245AF+910HGC

VG1245AG

4.7

Yes

VG1245AG+910HGC

VG1245AL

7.4

Yes

VG1245AL+910HGC

VG1245AN

11.7

No

VG1245AN+910HGC

VG1245BG

3/4

4.7

Yes

200

VG1245BG+910HGC

VG1245BL

7.4

Yes

VG1245BL+910HGC

VG1245BN

11.7

No

VG1245BN+910HGC

VG1245CL

1

7.4

Yes

200

VG1245CL+910HGC

VG1245CN

11.7

Yes

VG1245CN+910HGC

VG1245CP

18.7

No

VG1245CP+910HGC

VG1245DN

1-1/4

11.7

Yes

200

VG1245DN+910HGC

VG1245DP

18.7

Yes

VG1245DP+910HGC

VG1245DR

29.2

No

VG1245DR+910HGC

VG1245EP

1-1/2

18.7

Yes

200

VG1245EP+910HGC

VG1245ER

29.2

Yes

VG1245ER+910HGC

VG1245ES

46.8

No

VG1245ES+910HGC

VG1245FR

2

29.2

Yes

200

VG1245FR+910HGC

VG1245FS

46.8

Yes

VG1245FS+910HGC

VG1245FT

73.7

No

VG1245FT+910HGC

Table 5. Two-way stainless steel trim ball valves, non-spring return, VA9300 Series electric actuators without switches with optional M9000-561 Thermal Barrier
Fluid temperatures: -22°F to 284°F (-30°C to 140°C) water and 15 psi saturated steam AC/DC 24 V
On/off with timeout Floating with timeout DC 0(2) to 10 V

proportional

Valve

Size, in.

Cv

Characterizing disk

Closeoff psi

VA9310-HGA-2 with M9000-561 Thermal Barrier

VG1245DN

1-1/4

11.7 Yes

200

VG1245DNH910HGA

VG1245DP

18.7

Yes

VG1245DPH910HGA

VG1245DR

29.2

No

VG1245DRH910HGA

VG1245EP

1-1/2

18.7 Yes

200

VG1245EPH910HGA

VG1245ER

29.2 Yes

VG1245ERH910HGA

VG1245ES

46.8

No

VG1245ESH910HGA

VG1245FR

2

29.2 Yes

200

VG1245FRH910HGA

VG1245FS

48.8 Yes

VG1245FSH910HGA

VG1245FT

73.7 No

VG1245FTH910HGA

Table 6. Two-way stainless steel trim ball valves, non-spring return, VA9300 electric actuators with switches with optional M9000-561 Thermal Barrier
Fluid temperatures: -22°F to 284°F (-30°C to 140°C) water and 15 psi saturated steam AC/DC 24 V
On/off Floating DC 0(2) to 10 V

proportional

Valve

Size, in.

Cv

Characterizing disk

Closeoff psi

VA9310-HGA-2 Actuator with M9300-2 Switch Kit with M9000-561 Thermal Barrier 4

VG1245AA

1/2

0.3

Yes

200

VG1245AAH910HGC

VG1245AB 0.5 Yes

VG1245ABH910HGC

VG1245AC 0.8 Yes

VG1245ACH910HGC

VG1245AD 1.2 Yes

VG1245ADH910HGC

VG1245AE

1.9

Yes

VG1245AEH910HGC

VG1245AF

2.9

Yes

VG1245AFH910HGC

VG1245AG

4.7

Yes

VG1245AGH910HGC

VG1245AL

7.4

Yes

VG1245ALH910HGC

VG1245AN

11.7

No

VG1245ANH910HGC

VG1245BG

3/4

4.7

Yes

200

VG1245BGH910HGC

VG1245BL

7.4

Yes

VG1245BLH910HGC

VG1245BN

11.7

No

VG1245BNH910HGC

VG1245CL

1

7.

Yes

200

VG1245CLH910HGC

VG1245CN

11.7

Yes

VG1245CNH910HGC

VG1245CP

18.7

No

VG1245CPH910HGC

VG1245DN

1-1/4

11.7

Yes

200

VG1245DNH910HGC

VG1245DP

18.7

Yes

VG1245DPH910HGC

VG1245DR

29.2

No

VG1245DRH910HGC

VG1245EP

1-1/2

18.7

Yes

200

VG1245EPH910HGC

VG1245ER

29.2

Yes

VG1245ERH910HGC

VG1245ES

46.8

No

VG1245ESH910HGC

VG1245FR

2

29.2

Yes

200

VG1245FRH910HGC

VG1245FS

46.8

Yes

VG1245FSH910HGC

VG1245FT

73.7

No

VG1245FTH910HGC

1 To avoid excessive wear or drive time on the motor for the AGx models, use a controller or software that provides a timeout function to remove the signal at the end of rotation (stall).
2 To avoid excessive wear or drive time on the motor for the AGx models, use a controller or software that provides a timeout function to remove the signal at the end of rotation (stall).
3 For field mounting order VA9310-HGA-2 and the M9300-2 Switch Kit separately.
4 For field mounting order VA9310-HGA-2, M9300-2 Switch Kit, and M9000-561 Thermal Barrier separately.