Selection charts - Johnson Controls - LIT-1900471 - Flanged Globe or Ball Valve and Actuator - VG1000 Series Press End Connection Stainless Steel Trim Ball Valves

VG1000 Series Press End Connection Stainless Steel Trim Ball Valves Catalog Page

Brand
Johnson Controls
Product name
VG1000 Series Press End Connection Stainless Steel Trim Ball Valves
Document type
Catalog Page
Document number
LIT-1900471
Revision date
2021-02-11
Language
English
Table 1. VG1000 press end connection valves, plated brass trim, non-spring-return actuators
Valve code number Size, in. Cv (control port) / Cv (bypass port) Characterizing disk Closeoff psig AC 24 V
On/off (floating) without timeout1 On/off (floating) with timeout 0 to 10 VDC proportional
VA9104-AGA-xS2 VA9104-IGA-xS2 VA9104-GGA-xS2

Two-way

VG1291AA

1/2

0.3 Yes

200

VG1291AA+9T4AGA

-

VG1291AA+9T4GGA

VG1291AB 0.5 Yes

VG1291AB+9T4AGA

-

VG1291AB+9T4GGA

VG1291AC 0.8 Yes

VG1291AC+9T4AGA

-

VG1291AC+9T4GGA

VG1291AD

1.2

Yes

VG1291AD+9T4AGA

VG1291AD+9T4IGA

VG1291AD+9T4GGA

VG1291AE

1.9

Yes

VG1291AE+9T4AGA

VG1291AE+9T4IGA

VG1291AE+9T4GGA

VG1291AF

2.9

Yes

VG1291AF+9T4AGA

VG1291AF+9T4IGA

VG1291AF+9T4GGA

VG1291AG

4.7

Yes

VG1291AG+9T4AGA

VG1291AG+9T4IGA

VG1291AG+9T4GGA

VG1291AL

7.4

Yes

VG1291AL+9T4AGA

VG1291AL+9T4IGA

VG1291AL+9T4GGA

VG1291AN

11.7

No

VG1291AN+9T4AGA

VG1291AN+9T4IGA

VG1291AN+9T4GGA

VG1291BG

3/4

4.7

Yes

200

VG1291BG+9T4AGA

VG1291BG+9T4IGA

VG1291BG+9T4GGA

VG1291BL

7.4

Yes

VG1291BL+9T4AGA

VG1291BL+9T4IGA

VG1291BL+9T4GGA

VG1291BN

11.7

No

VG1291BN+9T4AGA

VG1291BN+9T4IGA

VG1291BN+9T4GGA

VG1291CL

1

7.4

Yes

200

VG1291CL+9T4AGA

VG1291CL+9T4IGA

VG1291CL+9T4GGA

VG1291CN

11.7

Yes

VG1291CN+9T4AGA

VG1291CN+9T4IGA

VG1291CN+9T4GGA

VG1291CP

18.7

No

VG1291CP+9T4AGA

VG1291CP+9T4IGA

VG1291CP+9T4GGA

Three-way

VG1891AA

1/2

0.3

Yes

200

VG1891AA+9T4AGA

-

VG1891AA+9T4GGA

VG1891AB

0.5

Yes

VG1891AB+9T4AGA

-

VG1891AB+9T4GGA

VG1891AC

0.8

Yes

VG1891AC+9T4AGA

-

VG1891AC+9T4GGA

VG1891AD

1.2

Yes

VG1891AD+9T4AGA

VG1891AD+9T4IGA

VG1891AD+9T4GGA

VG1891AE

1.9

Yes

VG1891AE+9T4AGA

VG1891AE+9T4IGA

VG1891AE+9T4GGA

VG1891AF

2.9

Yes

VG1891AF+9T4AGA

VG1891AF+9T4IGA

VG1891AF+9T4GGA

VG1891AG

4.7

Yes

VG1891AG+9T4AGA

VG1891AG+9T4IGA

VG1891AG+9T4GGA

VG1891AL

7.4

Yes

VG1891AL+9T4AGA

VG1891AL+9T4IGA

VG1891AL+9T4GGA

VG1891AN

11.7

No

VG1891AN+9T4AGA

VG1891AN+9T4IGA

VG1891AN+9T4GGA

VG1891BG

3/4

4.7

Yes

200

VG1891BG+9T4AGA

VG1891BG+9T4IGA

VG1891BG+9T4GGA

VG1891BL

7.4

Yes

VG1891BL+9T4AGA

VG1891BL+9T4IGA

VG1891BL+9T4GGA

VG1891BN

11.7

No

VG1891BN+9T4AGA

VG1891BN+9T4IGA

VG1891BN+9T4GGA

VG1891CL

1

7.4

Yes

200

VG1891CL+9T4AGA

VG1891CL+9T4IGA

VG1891CL+9T4GGA

VG1891CN

11.7

Yes

VG1891CN+9T4AGA

VG1891CN+9T4IGA

VG1891CN+9T4GGA

VG1891CP

18.7

No

VG1891CP+9T4AGA

VG1891CP+9T4IGA

VG1891CP+9T4GGA

Table 2. VG1000 Press End Connection Valves, Plated Brass Trim, Two-Way Spring-Return Actuators
Valve code number Size, in. Cv (control port) / Cv (bypass port) Characterizing disk Closeoff psig AC 24 V AC 120 V
Floating 0 to 10 VDC proportional On/off On/off
VA2202-AGA-2 VA2202-GGA-2 VA2202-BGA-2 VA2202-BAA-2

Two-way spring return valve open (normally open)

VG1291AA

1/2

0.3 Yes

200

VG1291AA+22TAGA

VG1291AA+22TGGA

VG1291AA+22TBGA

-
VG1291AB 0.5 Yes

VG1291AB+22TAGA

VG1291AB+22TGGA

VG1291AB+22TBGA

-
VG1291AC 0.8 Yes

VG1291AC+22TAGA

VG1291AC+22TGGA

VG1291AC+22TBGA

-

VG1291AD

1.2

Yes

VG1291AD+22TAGA

VG1291AD+22TGGA

VG1291AD+22TBGA

VG1291AD+22TBAA

VG1291AE

1.9

Yes

VG1291AE+22TAGA

VG1291AE+22TGGA

VG1291AE+22TBGA

VG1291AE+22TBAA

VG1291AF

2.9

Yes

VG1291AF+22TAGA

VG1291AF+22TGGA

VG1291AF+22TBGA

VG1291AF+22TBAA

VG1291AG

4.7

Yes

VG1291AG+22TAGA

VG1291AG+22TGGA

VG1291AG+22TBGA

VG1291AG+22TBAA

VG1291AL

7.4

Yes

VG1291AL+22TAGA

VG1291AL+22TGGA

VG1291AL+22TBGA

VG1291AL+22TBAA

VG1291AN

11.7

No

VG1291AN+22TAGA

VG1291AN+22TGGA

VG1291AN+22TBGA

VG1291AN+22TBAA

VG1291BG

3/4

4.7

Yes

200

VG1291BG+22TAGA

VG1291BG+22TGGA

VG1291BG+22TBGA

VG1291BG+22TBAA

VG1291BL

7.4

Yes

VG1291BL+22TAGA

VG1291BL+22TGGA

VG1291BL+22TBGA

VG1291BL+22TBAA

VG1291BN

11.7

No

VG1291BN+22TAGA

VG1291BN+22TGGA

VG1291BN+22TBGA

VG1291BN+22TBAA

VG1291CL

1

7.4

Yes

200

VG1291CL+22TAGA

VG1291CL+22TGGA

VG1291CL+22TBGA

VG1291CL+22TBAA

VG1291CN

11.7

Yes

VG1291CN+22TAGA

VG1291CN+22TGGA

VG1291CN+22TBGA

VG1291CN+22TBAA

VG1291CP

18.7

No

VG1291CP+22TAGA

VG1291CP+22TGGA

VG1291CP+22TBGA

VG1291CP+22TBAA

Two-way spring return valve closed (normally closed)

VG1291AA

1/2

0.3

Yes

200

VG1291AA+24TAGA

VG1291AA+24TGGA

VG1291AA+24TBGA

-
VG1291AB

0.5

Yes

VG1291AB+24TAGA

VG1291AB+24TGGA

VG1291AB+24TBGA

-
VG1291AC

0.8

Yes

VG1291AC+24TAGA

VG1291AC+24TGGA

VG1291AC+24TBGA

-

VG1291AD

1.2

Yes

VG1291AD+24TAGA

VG1291AD+24TGGA

VG1291AD+24TBGA

VG1291AD+24TBAA

VG1291AE

1.9

Yes

VG1291AE+24TAGA

VG1291AE+24TGGA

VG1291AE+24TBGA

VG1291AE+24TBAA

VG1291AF

2.9

Yes

VG1291AF+24TAGA

VG1291AF+24TGGA

VG1291AF+24TBGA

VG1291AF+24TBAA

VG1291AG

4.7

Yes

VG1291AG+24TAGA

VG1291AG+24TGGA

VG1291AG+24TBGA

VG1291AG+24TBAA

VG1291AL

7.4

Yes

VG1291AL+24TAGA

VG1291AL+24TGGA

VG1291AL+24TBGA

VG1291AL+24TBAA

VG1291AN

11.7

No

VG1291AN+24TAGA

VG1291AN+24TGGA

VG1291AN+24TBGA

VG1291AN+24TBAA

VG1291BG

3/4

4.7

Yes

200

VG1291BG+24TAGA

VG1291BG+24TGGA

VG1291BG+24TBGA

VG1291BG+24TBAA

VG1291BL

7.4

Yes

VG1291BL+24TAGA

VG1291BL+24TGGA

VG1291BL+24TBGA

VG1291BL+24TBAA

VG1291BN

11.7

No

VG1291BN+24TAGA

VG1291BN+24TGGA

VG1291BN+24TBGA

VG1291BN+24TBAA

VG1291CL

1

7.

Yes

200

VG1291CL+24TAGA

VG1291CL+24TGGA

VG1291CL+24TBGA

VG1291CL+24TBAA

VG1291CN

11.7

Yes

VG1291CN+24TAGA

VG1291CN+24TGGA

VG1291CN+24TBGA

VG1291CN+24TBAA

VG1291CP

18.7

No

VG1291CP+24TAGA

VG1291CP+24TGGA

VG1291CP+24TBGA

VG1291CP+24TBAA

Table 3. Three-Way Spring-Return Actuators
Valve code number Size, in. Cv (control port) / Cv (bypass port) Characterizing disk Closeoff psig AC 24 V AC 85-264V
Floating 0 to 10 VDC proportional On/off On/off
VA2202-AGA-2Z VA2202-GGA-2Z VA2202-BGA-2 VA2202-BAA-2

Three-way spring return counterclockwise, Port A (coil) open

VG1891AA

1/2

0.3

Yes

200

VG1891AA+22TAGA

VG1891AA+22TGGA

VG1891AA+22TBGA

-
VG1891AB

0.5

Yes

VG1891AB+22TAGA

VG1891AB+22TGGA

VG1891AB+22TBGA

-
VG1891AC

0.8

Yes

VG1891AC+22TAGA

VG1891AC+22TGGA

VG1891AC+22TBGA

-

VG1891AD

1.2

Yes

VG1891AD+22TAGA

VG1891AD+22TGGA

VG1891AD+22TBGA

VG1891AD+22TBAA

VG1891AE

1.9

Yes

VG1891AE+22TAGA

VG1891AE+22TGGA

VG1891AE+22TBGA

VG1891AE+22TBAA

VG1891AF

2.9

Yes

VG1891AF+22TAGA

VG1891AF+22TGGA

VG1891AF+22TBGA

VG1891AF+22TBAA

VG1891AG

4.7

Yes

VG1891AG+22TAGA

VG1891AG+22TGGA

VG1891AG+22TBGA

VG1891AG+22TBAA

VG1891AL

7.4

Yes

VG1891AL+22TAGA

VG1891AL+22TGGA

VG1891AL+22TBGA

VG1891AL+22TBAA

VG1891AN

11.7

No

VG1891AN+22TAGA

VG1891AN+22TGGA

VG1891AN+22TBGA

VG1891AN+22TBAA

VG1891BG

3/4

4.7

Yes

200

VG1891BG+22TAGA

VG1891BG+22TGGA

VG1891BG+22TBGA

VG1891BG+22TBAA

VG1891BL

7.4

Yes

VG1891BL+22TAGA

VG1891BL+22TGGA

VG1891BL+22TBGA

VG1891BL+22TBAA

VG1891BN

11.7

No

VG1891BN+22TAGA

VG1891BN+22TGGA

VG1891BN+22TBGA

VG1891BN+22TBAA

VG1891CL

1

7.4

Yes

200

VG1891CL+22TAGA

VG1891CL+22TGGA

VG1891CL+22TBGA

VG1891CL+22TBAA

VG1891CN

11.7

Yes

VG1891CN+22TAGA

VG1891CN+22TGGA

VG1891CN+22TBGA

VG1891CN+22TBAA

VG1891CP

18.7

No

VG1891CP+22TAGA

VG1891CP+22TGGA

VG1891CP+22TBGA

VG1891CP+22TBAA

Three-way spring return clockwise, Port B (bypass) open

VG1891AA

1/2

0.3

Yes

200

VG1891AA+24TAGA

VG1891AA+24TGGA

VG1891AA+24TBGA

-
VG1891AB

0.5

Yes

VG1891AB+24TAGA

VG1891AB+24TGGA

VG1891AB+24TBGA

-
VG1891AC

0.8

Yes

VG1891AC+24TAGA

VG1891AC+24TGGA

VG1891AC+24TBGA

-

VG1891AD

1.2

Yes

VG1891AD+24TAGA

VG1891AD+24TGGA

VG1891AD+24TBGA

VG1891AD+24TBAA

VG1891AE

1.9

Yes

VG1891AE+24TAGA

VG1891AE+24TGGA

VG1891AE+24TBGA

VG1891AE+24TBAA

VG1891AF

2.9

Yes

VG1891AF+24TAGA

VG1891AF+24TGGA

VG1891AF+24TBGA

VG1891AF+24TBAA

VG1891AG

4.7

Yes

VG1891AG+24TAGA

VG1891AG+24TGGA

VG1891AG+24TBGA

VG1891AG+24TBAA

VG1891AL

7.4

Yes

VG1891AL+24TAGA

VG1891AL+24TGGA

VG1891AL+24TBGA

VG1891AL+24TBAA

VG1891AN

11.7

No

VG1891AN+24TAGA

VG1891AN+24TGGA

VG1891AN+24TBGA

VG1891AN+24TBAA

VG1891BG

3/4

4.7

Yes

200

VG1891BG+24TAGA

VG1891BG+24TGGA

VG1891BG+24TBGA

VG1891BG+24TBAA

VG1891BL

7.4

Yes

VG1891BL+24TAGA

VG1891BL+24TGGA

VG1891BL+24TBGA

VG1891BL+24TBAA

VG1891BN

11.7

No

VG1891BN+24TAGA

VG1891BN+24TGGA

VG1891BN+24TBGA

VG1891BN+24TBAA

VG1891CL

1

7.4

Yes

200

VG1891CL+24TAGA

VG1891CL+24TGGA

VG1891CL+24TBGA

VG1891CL+24TBAA

VG1891CN

11.7

Yes

VG1891CN+24TAGA

VG1891CN+24TGGA

VG1891CN+24TBGA

VG1891CN+24TBAA

VG1891CP

18.7

No

VG1891CP+24TAGA

VG1891CP+24TGGA

VG1891CP+24TBGA

VG1891CP+24TBAA

1 To avoid excessive wear or drive time on the motor for the AGx models, use a controller or software that provides a timeout function to remove the signal at the end of rotation (stall).
2 Code numbers shown are for a VA9104-xGA-3S actuator with M3 screw terminals. To specify a 48-in. plenum rated cable, change 9T4 to 9A4 in the code number for a VA9104-xGA-2S actuator. For example, VG1241AD+9T4AGA becomes VG1241AD+9A4AGA.