| Valve size, in. (DN) | Valve code number | Actuator series | Linkage kit code number | Weather shield | ||||
|---|---|---|---|---|---|---|---|---|
| NPT end connection | Sweat end connection | Press end connection | Fluid temperatures <203°F (95°C) | Fluid temperatures <212°F (100°C) | Fluid temperatures +=212°F (100°C) | |||
| 1/2 (DN 15) |
VG1241Ax VG1841Ax |
— |
VG1291Ax VG1891Ax |
VA9104 | None required | Not rated | Not rated | M9000-342 |
| M9104 | Not available | |||||||
| VA9300 | None required | |||||||
| M9300 | M9310-500 | |||||||
| VA9203 | None required | |||||||
| M9203 | M9000-560 | |||||||
|
VG1245Ax VG1845Ax |
VG1275Ax VG1875Ax |
VG1295Ax VG1895Ax |
VA9104 | None required | M9000-561 | |||
| M9104 | Not available | |||||||
| VA9300 | None required | |||||||
| M9300 | M9310-500 | |||||||
| VA9203 | None required | |||||||
| M9203 | M9000-560 | |||||||
| 3/4 (DN 20) |
VG1241Bx VG1841Bx |
— |
VG1291Bx VG1891Bx |
VA9104 | None required | Not rated | Not rated | M9000-342 |
| M9104 | Not available | |||||||
| VA9300 | None required | |||||||
| M9300 | M9310-500 | |||||||
| VA9203 | None required | |||||||
| M9203 | M9000-560 | |||||||
|
VG1245Bx VG1845Bx |
VG1275Bx VG1875Bx |
VG1295Bx VG1895Bx |
VA9104 | None required | M9000-561 | |||
| M9104 | Not available | |||||||
| VA9300 | None required | |||||||
| M9300 | M9310-500 | |||||||
| VA9203 | None required | |||||||
| M9203 | M9000-560 | |||||||
| 1 (DN 25) |
VG1241Cx VG1841Cx |
VG1271Cx VG1871Cx |
VG1291Cx VG1891Cx |
VA9104 | None required | Not rated | Not rated | M9000-342 |
| M9104 | Not available | |||||||
| VA9300 | None required | |||||||
| M9300 | M9310-500 | |||||||
| VA9203 | None required | |||||||
| M9203 | M9000-560 | |||||||
|
VG1245Cx VG1845Cx |
VG1275Cx VG1875Cx |
VG1295Cx VG1895Cx |
VA9104 | None required | M9000-561 | |||
| M9104 | Not available | |||||||
| VA9300 | None required | |||||||
| M9300 | M9310-500 | |||||||
| VA9203 | None required | |||||||
| M9203 | M9000-560 | |||||||
| 1 1/4 (DN 32) |
VG1241Dx VG1841Dx |
— | — | VA9300 | None required | Not rated | Not rated | M9000-342 |
| M9300 | M9310-500 | |||||||
| VA9208 | None required | |||||||
| M9208 | M9000-550 | |||||||
|
VG1245Dx VG1845Dx |
VA9300 | None required | M9000-561 | |||||
| M9300 | M9310-500 | |||||||
| VA9208 | None required | |||||||
| M9208 | M9000-560 | |||||||
| 1 1/2 (DN 40) |
VG1241Ex VG1841Ex |
— | — | VA9300 | None required | Not rated | Not rated | M9000-342 |
| M9300 | M9310-500 | |||||||
| VA9208 | None required | |||||||
| M9208 | M9000-560 | |||||||
|
VG1245Ex VG1845Ex |
VA9300 | None required | M9000-561 | |||||
| M9300 | M9310-500 | |||||||
| VA9208 | None required | |||||||
| M9208 | M9000-560 | |||||||
| 2 (DN 50) |
VG1241Fx VG1841Fx |
— | — | VA9300 | None required | Not rated | Not rated | M9000-342 |
| M9300 | M9310-500 | |||||||
| VA9208 | None required | |||||||
| M9208 | M9000-560 | |||||||
|
VG1245Fx VG1845Fx |
VA9300 | None required | M9000-561 | |||||
| M9300 | M9310-500 | |||||||
| VA9208 | None required | |||||||
| M9208 | M9000-560 | |||||||
| Valve size, in. (DN) | Closeoff psig | Characterizing disc | Control port Cv (Kvs) | Bypass port Cv (Kvs) (Three-way only) | Plated brass ball and stem 23°F to 203°F (-5°C to 95°C) fluid temperature | Stainless steel ball and stem -22°F to 284°F (-30°C to 140°C) fluid temperature, 15 psi saturated steam | ||
|---|---|---|---|---|---|---|---|---|
| Two-way | Three-way | Two-way | Three-way | |||||
| NPT threaded end connection valves | ||||||||
| 1/2 (DN 15) | 200 | Yes | 0.3 (0.2) | 0.2 (0.1) | VG1241AA | VG1841AA | VG1245AA | VG1845AA |
| 0.5 (0.4) | 0.3 (0.2) | VG1241AB | VG1841AB | VG1245AB | VG1845AB | |||
| 0.8 (0.7) | 0.4 (0.3) | VG1241AC | VG1841AC | VG1245AC | VG1845AC | |||
| 1.2 (1) | 0.7 (0.6) | VG1241AD | VG1841AD | VG1245AD | VG1845AD | |||
| 1.9 (1.6) | 1.2 (1) | VG1241AE | VG1841AE | VG1245AE | VG1845AE | |||
| 2.9 (2.5) | 1.9 (1.6) | VG1241AF | VG1841AF | VG1245AF | VG1845AF | |||
| 4.7 (4) | 2.9 (2.5) | VG1241AG | VG1841AG | VG1245AG | VG1845AG | |||
| 7.4 (6.3) | 4.7 (4) | VG1241AL | VG1841AL | VG1245AL | VG1845AL | |||
| No | 11.7 (10) | 5.8 (5) | VG1241AN | VG1841AN | VG1245AN | VG1845AN | ||
| 3/4 (DN 20) | Yes | 4.7 (4) | 2.9 (2.5) | VG1241BG | VG1841BG | VG1245BG | VG1845BG | |
| 7.4 (6.3) | 4.7 (4) | VG1241BL | VG1841BL | VG1245BL | VG1845BL | |||
| No | 11.7 (10) | 5.8 (5) | VG1241BN | VG1841BN | VG1245BN | VG1845BN | ||
| 1 (DN 25) | Yes | 7.4 (6.3) | 4.7 (4) | VG1241CL | VG1841CL | VG1245CL | VG1845CL | |
| 11.7 (10) | 5.8 (5) | VG1241CN | VG1841CN | VG1245CN | VG1845CN | |||
| No | 18.7 (16) | 9.4 (8) | VG1241CP | VG1841CP | VG1245CP | VG1845CP | ||
| 1 1/4 (DN 32) | Yes | 11.7 (10) | 5.8 (5) | VG1241DN | VG1841DN | VG1245DN | VG1845DN | |
| 18.7 (16) | 9.4 (8) | VG1241DP | VG1841DP | VG1245DP | VG1845DP | |||
| No | 29.2 (25) | 14.6 (12.5) | VG1241DR | VG1841DR | VG1245DR | VG1845DR | ||
| 1 1/2 (DN 40) | Yes | 18.7 (16) | 9.4 (8) | VG1241EP | VG1841EP | VG1245EP | VG1845EP | |
| 29.2 (25) | 14.6 (12.5) | VG1241ER | VG1841ER | VG1245ER | VG1845ER | |||
| No | 46.8 (40) | 23.4 (20) | VG1241ES | VG1841ES | VG1245ES | VG1845ES | ||
| 2 (DN 50) | Yes | 29.2 (25) | 14.6 (12.5) | VG1241FR | VG1841FR | VG1245FR | VG1845FR | |
| 46.8 (40) | 23.4 (20) | VG1241FS | VG1841FS | VG1245FS | VG1845FS | |||
| No | 73.7 (63) | 36.8 (31.5) | VG1241FT | VG1841FT | VG1245FT | VG1845FT | ||