Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
OBJECT_NAME |
X |
77 |
|||||
|
OBJECT_TYPE |
X |
79 |
|||||
|
OBJECT_IDENTIFIER |
X |
75 |
|||||
|
PROPERTY_LIST |
X |
371 |
|||||
|
OUT_OF_SERVICE |
X |
81 |
|||||
|
STATUS_FLAGS |
X |
111 |
|||||
|
EVENT_STATE |
X |
36 |
|||||
|
PRESENT_VALUE |
X |
85 |
X |
||||
|
INACTIVE_TEXT |
X |
46 |
X |
40 characters max |
|||
|
ACTIVE_TEXT |
X |
4 |
X |
40 characters max |
|||
|
COS_TIME |
X 1 |
16 |
|||||
|
COS_COUNT |
X1 |
15 |
X |
0–4,294,967,295 |
|||
|
STATE_COUNT_RESET |
X1 |
115 |
|||||
|
ELAPSED_ACTIVE_TIME |
X1 |
33 |
X |
0–4,294,967,295 |
|||
|
ACTIVE_TIME_ RESET |
X1 |
114 |
|||||
|
MIN_OFF_TIME |
X1 |
66 |
X |
0–604,800 |
|||
|
MIN_ON_TIME |
X1 |
67 |
X |
0–604,800 |
|||
|
PRIORITY_ARRAY |
X1 |
87 |
|||||
|
RELINQUISH_DEFAULT |
X1 |
104 |
X |
||||
|
CURRENT_COMMAND_PRIORITY |
X |
431 |
|||||
|
DESCRIPTION |
X |
28 |
X |
40 characters max |
|||
|
RELIABILITY |
X |
103 |
X 2 |
||||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
MSTP_BUS_TYPE |
X |
2589 |
Enumerated |
X |
0–3 |
||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
0–249 |
||
|
ATTRIBUTE_ID |
X |
3365 |
Enumerated |
||||
|
COMMAND_SIGNATURE |
X |
3366 | Unsigned | ||||
|
DEFAULT_ATTRIBUTE_VALUE |
X |
3633 |
Boolean |
||||
|
LAST_RELIABLE_CMD_SIG |
X |
3362 | Unsigned | ||||
|
PEER_REFERENCE |
X |
748 | Complex |
X |
|||
|
REFERENCED_DEVICE_INSTANCE |
X |
1691 |
Unsigned |
X |
0–4,194,303 | ||
|
DIRECTION |
X |
746 |
Enumerated |
||||
|
ERROR_STATUS |
X |
576 |
Enumerated |
||||
|
FAILSOFT |
X |
2567 |
Boolean |
X |
|||
|
IN_TEST |
X |
3368 |
Boolean |
||||
|
CURRENT_CMD_SIG |
X |
3378 | Unsigned | ||||
|
CURRENT_RELIABILITY |
X |
3377 |
Enumerated |
||||
|
STANDARD_NAME |
X |
3670 |
Enumerated |
||||
|
BACNET_EXPOSED |
X |
3807 |
Boolean |
X |
|||
|
LAST_RELIABLE_VALUE |
X |
3369 |
Boolean |
||||
|
DEFAULT_VALUE |
X |
3113 |
Boolean |
X |
|||
|
TEST_VAL |
X |
3371 |
Boolean |
||||
|
INPUT |
X |
513 |
Boolean |
||||
|
OUTPUT |
X |
663 |
Boolean |
||||
|
CURRENT_VALUE |
X |
3376 |
Boolean |
||||
|
OFFLINE |
X |
913 |
Boolean |
||||
|
RESTORE_COMMAND_PRIORITY |
X |
721 |
Bit String |
X |
|||
|
STATUS |
X |
512 |
Enumerated |
||||
|
STATES_TEXT |
X |
931 |
Enumerated |
||||
|
USER_NAME |
X |
2390 |
Character String |