Analog Value - Johnson Controls - LIT-12013604 - JC-VAV1507-0 - Variable air volume controller - VAV1507 Modular Assembly

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement

Brand
Johnson Controls
Product name
VAV1507 Modular Assembly
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013604
Revision date
2020-08-13
Product status
Active
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Analog Value

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

     

OUT_OF_SERVICE

X

   

81

     

STATUS_FLAGS

X

   

111

     

EVENT_STATE

X

   

36

     

PRESENT_VALUE

X

   

85

 

X

 

UNITS

X

   

117

 

X

0 to 65,535

RELINQUISH_DEFAULT

 

X

 

104

 

X

 

PRIORITY_ARRAY

 

X

 

87

     

CURRENT_COMMAND_PRIORITY

 

X

 

431

     

COV_INCREMENT

 

X

 

22

 

X 1

any value > = 0

DESCRIPTION

 

X

 

28

 

X

40 characters max

MIN_PRES_VALUE

 

X

 

69

 

X

 

MAX_PRES_VALUE

 

X

 

65

 

X

 

RELIABILITY

 

X

 

103

 

X1

 

DISPLAY_PRECISION

   

X

661

Enumerated

X

0 to 12

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0 to 3

ITEM_REFERENCE

   

X

32527

Character String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

0 to 249

ALARM_STATE

   

X

1006

Enumerated

   

ATTRIBUTE_ID

   

X 2

3365

Enumerated

   

COMMAND_SIGNATURE

   

X2

3366

Unsigned

   

DEFAULT_ATTRIBUTE_VALUE

   

X2

3633

Boolean

   

LAST_RELIABLE_CMD_SIG

   

X2

3362

Unsigned

   

PEER_REFERENCE

   

X2

748

Complex

X

 

DIRECTION

   

X2

746

Boolean

   

ERROR_STATUS

   

X2

576

Boolean

   

FAILSOFT

   

X2

2567

Boolean

X

 

IN_TEST

   

X2

3368

Boolean

   

CURRENT_CMD_SIG

   

X2

3378

Unsigned

   

CURRENT_RELIABILITY

   

X2

3377

Enumerated

   

STANDARD_NAME

   

X2

3670

Enumerated

   

RESTORE_COMMAND_PRIORITY

   

X

721

Bit String

X

 

BACNET_EXPOSED

   

X

3807

Boolean

X

 

LAST_RELIABLE_VALUE

   

X2

3369 Real    

DEFAULT_VALUE

   

X2

3113 Real

X

 

TEST_VAL

   

X2

3371 Real    

INPUT

   

X2

513 Real    

OUTPUT

   

X2

663 Real    

CURRENT_VALUE

   

X2

3376 Real    

OFFLINE

   

X2

913

Boolean

   

STATUS

   

X

512

Enumerated

   

USE_COV_MIN_SEND_TIME

   

X2

3930

Boolean

X

 

USER_NAME

   

X

2390

Character String

 
1 Not writable in all instances.
2 Not Present in all instances.