|
Point Name |
Description |
TDA Module Point (Type/Instance ID) |
Enum Set/Range |
|---|---|---|---|
|
Supply Temp 1 Resistance (CWS1-R) |
The raw resistance measured by input 1 of TDA module. |
AI25000 |
3,000.0 to 55,000.0 ohms |
|
Gain term for Field Calibration of CWS1 (CWS1-GAIN) |
Field calibration gain value used to compensate for any error in the input 1 circuitry. |
AV25001 |
1E-16 to 2 |
|
Zero Reference for Field Calibration of CWS1 (CWS1-Zero Reference) |
Field calibration Zero Reference value used to compensate for any error in the input 1 circuitry. |
AV25002 |
-1000 to 1000ohms |
|
Temp Conversion Coefficient for CWS1 (CWS1-COEFFICIENT A) |
The first coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 1 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25003 |
-1 to 1 |
|
Temp Conversion Coefficient for CWS1 (CWS1-COEFFICIENT B) |
The second coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 1 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25004 |
-1 to 1 |
|
Temp Conversion Coefficient for CWS1 (CWS1-COEFFICIENT C) |
The third coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 1 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25005 |
-1 to 1 |
|
Chilled Water Supply 1 Temperature (CWS1-T) |
Temperature measured by input 1 of TDA module. |
AV25006 |
-10°C to 218°C |
|
CWS1 Calibrated Resistance (CWS1-R CALIBRATED) |
Resistance measured by input 1 of TDA module after Gain Term for Field Calibration of CWS1and Zero Reference for Field calibration of CWS1have been applied to Supply Temp 1 Resistance. |
AV25007 |
3,000.0 to 55,000.0ohms |
|
Return Temp 1 Resistance (CWR1-R) |
The raw resistance measured by input 2 of TDA module. |
AI25010 |
3,000.0 to 55,000.0ohms |
|
Gain term for Field Calibration of CWR1 (CWR1-GAIN) |
Field calibration gain value used to compensate for any error in the input 2 circuitry. |
AV25011 |
1E-16 to 2 |
|
Zero Reference for Field Calibration of CWR1 (CWR1-Zero Reference) |
Field calibration Zero Reference value used to compensate for any error in the input 2 circuitry. |
AV25012 |
-1000 to 1000ohms |
|
Temp Conversion Coefficient for CWR1 (CWR1-COEFFICIENT A) |
The first coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 2 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25013 |
-1 to 1 |
|
Temp Conversion Coefficient for CWR1 (CWR1-COEFFICIENT B) |
The second coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 2 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25014 |
-1 to 1 |
|
Temp Conversion Coefficient for CWR1 (CWR1-COEFFICIENT C) |
The third coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 2 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25015 |
-1 to 1 |
|
Chilled Water Return 1 Temperature (CWR1-T) |
Temperature measured by input 2 of TDA module. |
AV25016 |
-10°C to 218°C |
|
CWR1 Calibrated Resistance (CWR1-R CALIBRATED) |
Resistance measured by input 2 of TDA module after Gain Term for Field Calibration of CWR1and Zero Reference for Field calibration of CWR1have been applied to Return Temp 1 Resistance. |
AV25017 |
3,000.0 to 55,000.0ohms |
|
Supply Temp 2 Resistance (CWS2-R) |
The raw resistance measured by input 3 of TDA module. |
AI25020 |
3,000.0 to 55,000.0ohms |
|
Gain term for Field Calibration of CWS2 (CWS2-GAIN) |
Field calibration gain value used to compensate for any error in the input 3 circuitry. |
AV25021 |
1E-16 to 2 |
|
Zero Reference for Field Calibration of CWS2 (CWS2-Zero Reference) |
Field calibration Zero Reference value used to compensate for any error in the input 3 circuitry. |
AV25022 |
-1000 to 1000ohms |
|
Temp Conversion Coefficient for CWS2 (CWS2-COEFFICIENT A) |
The first coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 3 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25023 |
-1 to 1 |
|
Temp Conversion Coefficient for CWS2 (CWS2-COEFFICIENT B) |
The second coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 3 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25024 |
-1 to 1 |
|
Temp Conversion Coefficient for CWS2 (CWS2-COEFFICIENT C) |
The third coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 3 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25025 |
-1 to 1 |
|
Chilled Water Supply 2 Temperature (CWS2-T) |
Temperature measured by input 3 of TDA module. |
AV25026 |
-10°C to 218°C |
|
CWS2 Calibrated Resistance (CWS2-R CALIBRATED) |
Resistance measured by input 3 of TDA module after Gain Term for Field Calibration of CWS2and Zero Reference for Field calibration of CWS2have been applied to Supply Temp 2 Resistance. |
AV25027 |
3,000.0 to 55,000.0ohms |
|
Return Temp 2 Resistance (CWR2-R) |
The raw resistance measured by input 4 of TDA module. |
AI25030 |
3,000.0 to 55,000.0ohms |
|
Gain term for Field Calibration of CWR2 (CWR2-GAIN) |
Field calibration gain value used to compensate for any error in the input 4 circuitry. |
AV25031 |
1E-16 to 2 |
|
Zero Reference for Field Calibration of CWR2 (CWR2-Zero Reference) |
Field calibration Zero Reference value used to compensate for any error in the input 4 circuitry. |
AV25032 |
-1000 to 1000ohms |
|
Temp Conversion Coefficient for CWR2 (CWR2-COEFFICIENT A) |
The first coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 4 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25033 |
-1 to 1 |
|
Temp Conversion Coefficient for CWR2 (CWR2-COEFFICIENT B) |
The second coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 4 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25034 |
-1 to 1 |
|
Temp Conversion Coefficient for CWR1 (CWR2-COEFFICIENT C) |
The third coefficient of the Steinhart-Hart equation, used to convert the measured resistance on input 4 to equivalent temperature. This value can be found on the calibration certificate for the temperature probe connected to this input. |
AV25035 |
-1 to 1 |
|
Chilled Water Return 2 Temperature (CWR2-T) |
Temperature measured by input 4 of TDA module. |
AV25036 |
-10°C to 218°C |
|
CWR2 Calibrated Resistance (CWR2-R CALIBRATED) |
Resistance measured by input 4 of TDA module after Gain Term for Field Calibration of CWR2and Zero Reference for Field calibration of CWSRhave been applied to Return Temp 2 Resistance. |
AV25037 |
3,000.0 to 55,000.0ohms |
|
Return-Supply Temperature 1 Difference 1 (RETURN SUPPLY1-DIFF) |
Difference between temperatures Chilled Water Return 1 Temperatureand Chilled Water Supply 1 Temperature. |
AV25040 |
-40°C to 40°C |
|
Return-Supply Temperature 2 Difference 2 (RETURN SUPPLY2-DIFF) |
Difference between temperatures Chilled Water Return 2 Temperatureand Chilled Water Supply 2 Temperature. |
AV25041 |
-40°C to 40°C |
|
Verification Mode Enable 3 (VERIFICATION-MODE-EN) |
When enabled, the Input Output Update Interval is overridden, and all points update at a 10 second interval. Intended to be used temporarily when faster data reporting is desired. |
BV25050 |
1 - Disable 2 - Enable |
|
Input Output Update Interval (IO-INTERVAL) 4 |
Data reporting rate for all points. |
AV25051 |
Update rate:
|
|
Fault Reset (FAULT-RESET) 5 |
Resets fault conditions on all inputs, including the fault LEDs and sensor fault points. |
BV25052 |
1 - Off 2 - Reset |
|
CWS1 Sensor Fault (CWS1-FAULT) |
Indicates a fault condition was detected on input 1 of the device. The point will latch to the active state until the Fault Resetpoint is commanded to reset. |
BO25060 |
1 - Inactive 2 - Active |
|
CWR1 Sensor Fault (CWR1-FAULT) |
Indicates a fault condition was detected on input 2 of the device. The point will latch to the active state until the Fault Resetpoint is commanded to reset. |
BO25061 |
1 - Inactive 2 - Active |
|
CWS2 Sensor Fault (CWS2-FAULT) |
Indicates a fault condition was detected on input 3 of the device. The point will latch to the active state until the Fault Resetpoint is commanded to reset. |
BO25062 |
1 - Inactive 2 - Active |
|
CWR2 Sensor Fault (CWR2-FAULT) |
Indicates a fault condition was detected on input 4 of the device. The point will latch to the active state until the Fault Resetpoint is commanded to reset. |
BO25063 |
1 - Inactive 2 - Active |
1 The Return-Supply Temperature 1
Difference present value is the difference between the present
values of the CWS1-T and CWR1-T points.
2 The Return-Supply Temperature 2
Difference present value is the difference between the present
values of the CWS2-T and CWR2-T points.
3 Verification Mode Enable may be used
to temporarily accelerate the reporting rate of temperature and
resistance data to 10-second intervals. This is intended to be used
for system verification only. Enabling verification mode on multiple
units simultaneously may degrade communication bus performance.
4 Input Output Update Interval
controls the rate at which the TE-74 reports measurements.
Decreasing this value may degrade communications bus
performance.
5 Fault Reset resets fault indication
points (CWS1-FAULT, CWR1-FAULT, CWS2-FAULT, and CWR2-FAULT) and
fault indication LEDs. These fault indication points latch to the
Active state when a fault is detected on an input channel. These
fault indication points provide simple visual indication of
potential system performance issues and will remain active until
reset.